background image

31

b) Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered 

in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, 

terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.

•  Ensure that apparatus is mounted securely.
•  Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the 

ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer s specifications.

 NOTE

The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Instrinsically safe 

components do not have to be isolated prior to working on them.

11) Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the 

permissible voltage and current permitted for the equipment in use. Intrinscially safe components are the only types that can 

be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace 

components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere 

from a leak.

12) Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse 

environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as 

compressors or fans.

13) Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide 

torch (or any other detector using a naked flame) shall not be used.

14) Leak detection methods

The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak 

detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration.

(Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition 

and is suitable for the refrigerant. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall 

be calibrated to the refrigerant employed and the appropriate percentage of gas (25% maximum) is confirmed. Leak detection 

fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine 

may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected ,all naked flames shall be removed or 

extinguished. If a leakage of refrigernat is found which requires brazing, all of the refrigerant shall be recovered from the system, 

or isolated(by means of shut off valves) in a part of the system remote from the leak . Oxygen free nitrogen(OFN) shall then be 

purged through the system both before and during the brazing process.

15) Removal and evacuation

When breaking into the refrigerant circuit to make repairs of for any other purpose conventional procedures shall be used, 

However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be 

adhered to:
•  Remove refrigerant;
•  Purge the circuit with inert gas;
•  Evacuate;
•  Purge again with inert gas;
•  Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render 

the unit safe. This process may need to be repeated several times.

Compressed air or oxygen shall not be used for this task. 

Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is 

achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant 

is within the system.

When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This 

operation is absolutely vital if brazing operations on the pipe-work are to take place. 

Ensure that the outlet for the vacuum pump is not closed to any ignition sources and there is ventilation available.

16) Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed:

•  Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be 

as short as possible to minimize the amount of refrigerant contained in them.

Summary of Contents for Aquantia KHPMS-BI Series

Page 1: ...asing our product Before using your unit please read this manual carefully and keep it for future reference INSTALLATION OWNER S MANUAL Aquantia Air Water Heat Pumps KHPMS BI Set Outdoor Unit KHP BI 4...

Page 2: ...ts 09 6 3 Drain hole position 10 6 4 Servicing space requirements 10 7 INSTALLATION THE CONNECTING PIPE 11 7 1 Refrigerant piping 11 7 2 Leakage Detection 12 7 3 Heat insulation 12 7 4 Connecting meth...

Page 3: ...TURN OVER TO CUSTOMER 22 13OPERATION AND PERFORMANCE 24 13 1 Protection equipment 24 13 2 About power cut 24 13 3 Heating capacity 24 13 4 Compressor protection feature 24 13 5 Cooling and heating op...

Page 4: ......

Page 5: ...01 8 10 kW 4 6 kW 8 10 kW 4 6 kW Please remove the hollow plate after installation Electric Control System Refrigerant System Wiring diagram 8 10kW for example...

Page 6: ...sistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants DANGER Indicates an imminently hazardous situation which if...

Page 7: ...ks and fire Make sure all wiring is secure Use the specified wires and ensure that terminal connections or wires are protected from water and other adverse external forces Incomplete connection or aff...

Page 8: ...able If electrical appliances are disposed of in landfills or dumps hazardous substance can leak into the groudwater and get into the food chain damaging your health and well being The wiring must be...

Page 9: ...l data manual 1 Water outlet connection pipe assembly 1 Energy label 1 3 BEFORE INSTALLATION Before installation Be sure to confirm the model name and the serial number of the unit Handling 1 Handle t...

Page 10: ...he grips in the fan grills to avoid damage The unit is top heavy Prevent the unit from falling due to improper inclination during handling 4 IMPORTANT INFORMATION FOR THE REFRIGERANT This product has...

Page 11: ...nit can be installed at an even level Places where there is no possibility of flammable gas or product leak The equipment is not intended for use in a potentially explosive atmosphere Places where ser...

Page 12: ...prevent exposure to wind install the unit with its suction side facing the wall Never install the unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind inst...

Page 13: ...075 363 411 625 184 126 179 965 117 6 2 Installation requirements Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during the operation In...

Page 14: ...drain hole has opened It is suggested to site the unit with the base electric heater 6 4 Installation space requirements 6 4 1 In case of stacked installation 1 In case obstacles exist in front of the...

Page 15: ...nstalling multiple units in lateral connection per row Fig 6 8 Unit A mm B1 mm B2 mm C mm 4 10kW 3000 2000 300 600 7 INSTALL THE CONNECTING PIPE Check whether the difference in height between the indo...

Page 16: ...e while back side getting out pipes 7 2 Leakage Detection Use soap water or leakage detector to check every joint whether leak or not Refer to Fig 7 2 Note A is high pressure side stop valve B is low...

Page 17: ...l difference is greater than 20m it is recommended that an oil return bend with dimensions as specified in Figure 7 4 is set every 5m in the gas pipe of the main pipe and ii if the outdoor unit is bel...

Page 18: ...igh low pressure valves before charging pressured nitrogen Charge pressure nitrogen from the connector on the pressure valves The airtight testing should never use any oxygen flammable gas or poisonou...

Page 19: ...contact with the piping particularly on the high pressure side Make sure no external pressure is applied to the terminal connectors When installing the ground fault circuit interrupter make sure that...

Page 20: ...2 5 10 and 16 1 5 and 2 5 1 5 and 4 16 and 25 2 5 and 4 2 5 and 6 25 and 32 4 and 6 4 and 10 32 and 50 6 and 10 6 and 16 50 and 63 10 and 16 10 and 25 Table 8 2 System Outdoor Unit Power Current Compr...

Page 21: ...igh speed type breaker of 30 mA 0 1 s Please use 3 core shielded wire 8 5 To finish the outdoor unit installation insulate and fix the refrigerant piping and interconnection cable as follows A Gas pip...

Page 22: ...itch off all power i e unit power supply and backup heater and domestic hot water tank power supply if applicable before removing doors 1 Parts inside the unit may be hot Push the grill to the left un...

Page 23: ...19 PCB A PCB B 8 10kW 9 8 6 4 5 7 1 2 3 NOTE The picture is for reference only please refer to the actual product 9 3 4 10kW units 1 PCB A Inverter module...

Page 24: ...n with hydro box control board CN29 4 Port for IC programming CN32 18 Reserved CN30 5 Port for ground wire CN37 19 Port for communication with PCB A CN17 6 Input port for neutral wire CN10 20 Port for...

Page 25: ...uirements for charge limits in unventilated areas The maximum refrigerant charge in appliance shall be in accordance with the following mmax 2 5 x LFL 5 4 x 1 8 x A 1 2 or the required minium floor ar...

Page 26: ...gerant Indoor unit Room is filled of leakage refrigerant All refrigerant has leaked out 8 10kW Indoor Unit Outdoor Unit Fig 11 2 Fig 11 3 12 TURN OVER TO CUSTOMER The owner s manual of indoor unit and...

Page 27: ...ut below the limit Otherwise oxygen in the room may be affected resulting in a serious accident The refrigerant in the heat pump is safe and normally does not leak If the refrigerant leaks in the room...

Page 28: ...rosting automatically about 2 10 minutes and then water will be drained out from outdoor unit During defrosting the fan motors in the outdoor unit will stop running Never expose little children plants...

Page 29: ...ke the connector dry Add waterproof adhesive 3 The Th sensor failure change a new sensor Discharge temperature sensor Tp error 1 The Tp sensor connector is loosen Re connect it 2 The Tp sensor connect...

Page 30: ...t 2 Pressure sensor failure change a new sensor The main control board PCB B EEprom failure 1 The EEprom parameter is error rewrite the EEprom data 2 EEprom chip part is broken change a new EEprom chi...

Page 31: ...1 The same reason to P1 2 TW_out temp sensor is loosen Reconnect it 3 T1 temp sensor is loosen Reconnect it 4 T5 temp sensor is loosen Reconnect it Module protection 1 Power supply voltage of the uni...

Page 32: ...he power supply 2 If the power supply is OK and check if LED light is OK check the voltage PN if it is 380V the problem usually comes from the main board And if the light is OFF disconnect the power c...

Page 33: ...Fan motor DC motor Horizontal Compressor DC inverter dual rotary Heat exchanger Fin coil Refrigerant Type R32 Quantity 1 55kg 1 65kg Weight Net weight 57kg 67kg Gross weight 68kg 79kg Connections Gas...

Page 34: ...g the period that the work is carried out The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere 8 Checks to the refrigeration equipment...

Page 35: ...is not a potential source of ignition and is suitable for the refrigerant Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigeran...

Page 36: ...ce or decommissioning it is recommended good practice that all refrigerants are removed safely When tranferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders a...

Page 37: ...Outdoor temperature sensor 2 4 Way Valve 11 Outdoor exchanger sensor 3 Gas liquid separator 12 Stop valve gas 4 Air side heat exchanger 13 Stop valve liquid 5 Electronic expansion Valve 14 High Press...

Page 38: ...E_COOL CHECK NO COM L OUT PCB A Inverter board for 1phase PCB B Main control board for 1phase SW1 SW2 SW3 T3 T4 Tp EEV CN9 XP1 XS2 XP2 CN8 XS1 CN33 SV6 CN5 Th CN1 H_SEN CN4 TF CN14 4 WAY BLUE CN6 BLUE...

Page 39: ...35 16125300002239 V1 0...

Page 40: ......

Reviews: