62
Error code and
description
POSSIBLE CAUSES
POSSIBLE SOLUTIONS
E9:
Wired controller and IDU
communication fault
No address set for the IDU or IDU adress duplicated
Set an address for the IDU; duplicated IDU
addresses are not allowed in the same system.
Main/secondary wired controller not set when two wired
controllers
control one or multiple IDUs
Set one wired controller to secondary wired
controller.
The D1/D2 line sequence of secondary wired controller is
inconsistent with that of the main
wired controller
Exchange the D1/D2 line sequence of secondary
wired controller.
Wired controller damaged
Replace the wired controller.
IDU board fault
Replace the IDU board.
F7:
Wired controller
EEPROM fault
EEPROM data error
Press “MODE” + “MENU” + “TEMP UP” + “TEMP
DOWN” for more than 3 seconds to reset the wired
controller until the default status appears.
Wired controller damaged
Replace the wired controller.
For any “Group”, the
number of IDUs may
not be consist- ent with
the actual number of
connected IDUs.
D1/D2 communication wiring error or bad contact in
individual IDU.
IDU address has not been set or
duplicate address.
Check and adjust the D1/D2
communication line
Set the IDU address. No duplicate IDU addresses in
the same system.
Main-secondary wired controllers
have not been set.
Set one wired controller to be the secondary wired
controller.
Board failure in individual IDU.
Replace the board of affected IDU.