MCAC-ATSM-2017-08 Aqua Tempo Power Series (with LAK) air cooled scroll chiller unit (50Hz)
39
8 Electric Characteristics
Model
Outdoor Unit
Power Supply
Compressor
OFM
Hz
Voltage
Min.
Max.
TOCA
MFA
LRA(each)
RLA(each)
KW
FLA
KEM-30 DHN3
50
380-415
342
456
21.1
36
74
10.6/11.8
0.67
3.1
KEM-65 DHN3
50
380-415
342
456
54.5
70
144/82.4/74 21.1/12.7/11.8
0.865(×2)
4.0(×2)
KEM-130 HN3
50
380-400
342
440
109
150
147
21.4
0.865(×4)
4.0(×4)
KEM-200 HN3
50
380-400
342
440
150
200
147
21.4
0.865(×6)
4.0(×6)
KEM-250 HN3
50
380-400
342
440
200
300
142
20.7
0.8(×8)
3.7(×8)
Remark:
TOCA: Total Over-current Amps. (A)
MFA: Max. Fuse Amps. (A)
LRA: Locked Rotor Amps. (A)
RLA: Rated Load Amps. (A)
OFM: Outdoor Fan Motor.
KW: Rated Motor Input (kW)
FLA: Full Load Amps.