2) Low pressure protection
Low pressure protection.
No
Discharge temperature
protection.
Discharge temperature
switch is broken or joint
is loose.
Yes
Yes
Replace
discharge
temperature
switch,
fixed joint.
Yes
Yes
Yes
Yes
No
No
No
No
Detect leakage for all
system,
append
refrigerant.
Refrigerant is too less.
Replace the EXV or coil.
Cause of dirty and
blocked, replace the
EXV, capillary and filter.
Vacuuming and append
refrigerant if ice blocked.
Check
if
happened
frequently, if yes, please
replace PCB.
Couldn’t open the EXV.
The EXV, capillary and filter
are dirty, blocked and ice
blocked.
PCB mistakes to alarm.
Inform the customer
service center.
Refrigerant is too less.
Inspect leakage in system,
append refrigerant.
Replace the EXV and coil.
Cause of dirty and blocked,
replace the EXV, capillary and
filter. Vacuuming and append
refrigerant if ice blocked.
Inspect if the water flow is
normal, refer to the water flow
malfunction to analysis.
Couldn’t open the EXV.
The EXV, capillary and filter are
dirty, blocked and ice blocked.
The pressure controller is
broken or joint is loose.
Anti-freezing lower pressure
protection.
Inform the customer service
center.
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Replace
the
pressure
controller, fixed joint.
Summary of Contents for KEM-30 DNH3
Page 2: ......
Page 5: ...2 1 2 External appearance KEM 130 HN3 KEM 200 HN3 KEM 250 HN3 KEM 30 DHN3 KEM 65 DHN3 ...
Page 33: ...30 130kW module ...
Page 35: ...32 250kW module ...
Page 39: ...36 200kW module ...
Page 73: ...130kW module 200kW module Input of airflow Input of airflow Input of airflow Input of airflow ...
Page 159: ......
Page 160: ......