4.29 P3 Troubleshooting
4.29.1 Digital display output
4.29.2 Description
▪ High temperature protection of ambient temperature sensor in cooling mode. When the ambient temperature is
higher than 65°C, the system displays P3 protection and all units stop running. When the ambient temperature returns
drops below 58°C, P3 is removed and normal operation resumes.
▪ All units stop running.
▪ Error code is displayed on main PCB and user interface.
4.29.3 Possible causes
▪ Ambient temperature sensor is not connected properly or has malfunctioned.
▪ Fan motor wiring connection is wrong.
▪ Poor condenser heat exchange.
▪ Fan motor damaged.
▪ Main PCB damaged.