53
Part 4 - Diagnosis and T
roubleshooting
Table 4-3.1: Error Code Table (30kW and 60kW units) (continued)
Fd
74
Suction temperatrue sensor error
Displayed on main PCB and user
interface
xFF
76
DC fan failure
Displayed on main PCB and user
interface
FP
79
DIP inconsistency of multiple water pumps
Displayed on main PCB and user
interface
C7
88
If PL occurs 3 times,the system reports the C7 failure
Displayed on main PCB and user
interface
L0
101
Compressor inverter module protection
Displayed on only user interface
L1
102
DC bus low voltage protection
Displayed on only user interface
L2
103
DC bus high voltage protection
Displayed on only user interface
L4
105
MCE error
Displayed on only user interface
L5
106
Zero speed protection
Displayed on only user interface
L7
108
Phase sequence lost protection
Displayed on only user interface
L8
109
Compressor frequency change over 15Hz
Displayed on only user interface
L9
110
Compressor frequency difference 15Hz
Displayed on only user interface
dF
146
Defrosting prompt
Displayed on main PCB and user
interface
Note:
1. When the error code appears, the error code corresponding to the error code can be obtained through the H1H2 port by using the host computer to
query the wired controller register.