4.14 P7 Troubleshooting
4.14.1 Digital display output
4.14.2 Description
▪ High temperature protection of air side heat exchanger refrigerant outlet temperature sensor or air side heat
exchanger refrigerant total outlet temperature sensor in cooling mode. When the air side heat exchanger refrigerant
outlet temperature is higher than 60°C or air side heat exchanger refrigerant total outlet temperature is higher
than 61°C for more than 3 seconds, the system displays P7 protection and all units stop running. When the air side
heat exchanger refrigerant outlet temperature drops below 50°C or air side heat exchanger refrigerant total outlet
temperature drops below 58°C, P7 is removed and normal operation resumes.
▪ All units stop running.
▪ Error code is displayed on main PCB and user interface.
4.14.3 Possible causes
▪ Air side heat exchanger refrigerant outlet temperature sensor or air side heat exchanger refrigerant total outlet
temperature sensor not connected properly or has malfunctioned.
▪ Fan motor wiring connection is wrong.
▪ Poor condenser heat exchange.
▪ Fan motor damaged.
▪ Main PCB damaged.