42
12 APPLICABLE MODELS AND MAIN PARAMETERS
Table 12-1
Model
KEM-30 DRS4.1
KEM-60 DRS4.1
KEM-90 DRS5
Cooling capacity
kW
27.5
55.0
82.0
Heating capacity
kW
32.0
62.0
90.0
Standard cooling input
kW
10.3
21.5
27.8
Cooling rated current
A
15.9
33.1
42.9
Standard heating input
kW
10.0
20.0
28.1
Heating rated current
A
15.4
30.8
43.3
Power supply
380-415V 3N~ 50Hz
Operation control
Control of wired controller, auto startup, running state display, failure alert etc.
Safety device
High or low pressure switch, freeze-proof device, water flow volume controller, Overcurrent
device, power phase sequence device etc.
Refrigerant
Type
R32
Chargeing volume kg
7.9
14.0
16.0
Water pipe system
Waterflow volume m
3
/h
5.0
9.8
15.0
Hydraulic resistance lose
kPa
55
61
75
Hydraulic resistance lose
kPa
Plate heat exchanger
Max. pressure MPa
1.0
Min. pressure MPa
0.05
Inlet and outlet pipe dia.
DN40
DN50
Air side heat exchanger
Type
Fin coil model
Air flow volume m
3
/h
12500
24000
35000
Outline dimension N.W. of
the unit
L mm
1870
2220
2220
W mm
1000
1055
1135
H mm
1175
1325
2315
Net Weight
kg
300
480
635
Operation Weight
kg
310
490
650
Packing dimension
L × W × H mm
1910×1035×1225
2250×1090×1370
2250×1180×2445
Summary of Contents for KEM-90 DRS5