17
NO.
Detail information
16
CN33: COMP-STATE,connect with an ac light to indicate the state of the compressor
Attention: the control port value of the COMP-STATE actually detected is ON/OFF but not 220-230V control power
supply, so special attention should be paid when installing the light.
17
CN2
HEAT1.Pipeline Auxiliary Heater
HEAT2: Water tank Auxiliary Heater
Attention: the control port value of the HEAT1 and HEAT2 actually detected is ON/OFF but not 220-230V control
power supply, so special attention should be paid when installing the pipeline and water tank auxiliary heater.
18
CN24
:
The alarm signal output of the unit (ON/OFF signal)
Attention: the control port value of the alarm actually detected is ON/OFF but not 220-230V control power supplyk so
special attention should be paid when installing the alarm signal output.
19
CN20: TP-PRO,Discharge temperature switch protection (protection code P0,provent the compressor from
over temperature 115°C)
20
CN71: EXVB,System electronic expansion valve2.Used for cooling.
21
CN72: EXVC,EVI electronic expansion valve.Used for EVI.
22
CN72: EXVC,EVI electronic expansion valve.Used for EVI.
23
CN60: Outdoor units communication or HMI conmunication port
24
CN61: Outdoor units communication or HMI conmunication port
25
CN64: Fan inverter module communication ports
26
CN65: Compressor inverter module communication ports
27
CN300: Program burn in port(WizPro200RS programming device).
28
IC10: EEPROM chip
29
CN1: temperature sensors input port.
T4: outdoor ambient temperature sensor
T3A/T3B: pipe temperature sensor of the condenser
T5: wtater tank temperature sensor
T6A: Refrigerant inlet temperature of EVI plate heat exchanger
T6B: Refrigerant outlet temperature of EVI plate heat exchanger
30
CN16: System pressure sensor
31
CN31: Temperature sensors input port
Th: System suction temperature sensor
Taf2: Water side antifreeze temperature sensor
Two: Unit water outlet temperature sensor
Twi: Unit water inlet temperature sensor
Tw: Total water outlet temperature sensor when several units are connected in parallel
32
CN69: Temperature sensors input port
Tp1: DC inverter compressor 1 discharge temperature sensor
Tp2: DC inverter compressor 2 discharge temperature sensor
Tz/7: coil final outlet temperature sensor
Taf1: Water side antifreeze temperature
33
CN19: Low voltage protection switch.(Protection code P1)
34
CN91: Three-phase protector output switch.(Protection code E8)
35
CN58: Fan realy driver port.
36
CN8: Remote function of cool/heat signal
37
CN8: Remote function of on/off signal
38
CN8: Water flow switch signal
39
SW3: Up button
a) Select different menus when enter menu selection.
b) For sopt inspection in conditions.
SW4:Down button
a) Select different menus when enter menu selection.
b) For sopt inspection in conditions.
SW5:Menu button
Press to enter menu selection, short press to return to the previous menu.
SW6:OK button
Enter the submenu or confirm the function selected by short pressing.
40
CN18:Program burn in port(USB).