1.  PRECAUTIONS

 

 

 

 

Be  sure  to  be  in  conformity  with  the  local,  national  and 
international laws and regulations.

 

 

Read "PRECAUTIONS" carefully before installation.

 

 

The  following  precautions  include  important  safety  items. 
Observe them and never forget.

 

Keep  this  manual  in  a  handy  place  for  future  reference. 

Before  out  from  factory,  FAN  COIL  UNIT  (AIR  UNITS)  has

 

passed Fan Coil Overpressure Resistant  Test,  Statically

 

and  Dynamically  Balanced  Adjustment,  Noise  Test,  Air 
(cool)  Volume  Test,  Electric  Property  Test,  Outline  Quality 
Detection.

 

 

This  appliance  can  be  used  by  children  aged  from  8  years 
and  above  and  persons  with  reduced  physical,  sensory  or 
mental  capabilities  or  lack  of  experience  and  knowledge  if 
they  have  been  given  supervision  or  instruction 
concerning  use  of  the  appliance  in  a  safe  way  and 
understand  the  hazards  involved.  Children  shall  not  play 
with  the  appliance.  Cleaning  and  user  maintenance  shall 
not be made by children without supervision.

 

 

 

 

The safety precautions listed here are divided into two categories. In 
either case, important safety information is listed which must be read 
carefully.

 

 

WARNING

 

 

Failure to observe a warning may result in serious injuries. 

 

CAUTION

 

 

Failure to observe a caution may result in injury or 
damage to the equipment.

 

 

After  completing  the  installation,  make  sure  that  the  unit  operates 
properly  during  the  start-up  operation.  Please  instruct  the  customer 
on how to operate the unit and keep it maintained.

 

 

 

 

WARNING

 

 

Be  sure  only  trained  and  qualified  service  personnel  to 
install, repair or service the equipment.

 

Improper  installation,  repair,  and  maintenance  may  result  in 
electric  shocks,  short-circuit,  leaks,  fire  or  other  damage  to 
the equipment.

 

Install according to this installation instructions strictly.

 

If  installation  is  defective,  it  will  cause  water  leakage, 
electrical shock and fire.

 

 

When  installing  the  unit  in  a  small  room,  take  measures 
against to keep refrigerant concentration  from exceeding 
allowable safety limits in the event of refrigerant leakage. 

Contact  the  place  of  purchase  for  more  information. 
Excessive refrigerant in  a closed  ambient can  lead  to  oxygen 
deficiency.

 

 

Use  the  attached  accessories  parts  and  specified  parts 
for installation.

 

otherwise,  it  will  cause  the  set  to  fall,  water  leakage, 
electrical shock and fire.

 

 

The appliance must be installed 2.3m above floor. 

The appliance shall not be installed in the laundry.

 

Before  obtaining  access  to  terminals,  all  supply  circuits 
must be disconnected.

 

 

The  appliance  must  be  positioned  so  that  the  plug  is 
accessible.

 

 

The  enclosure of the  appliance  shall be  marked by word, 
or by symbols, with the direction of the fluid flow.

 

 

For  electrical  work,  follow  the  local  national  wiring 
standard, regulation and this  installation instructions. An 
independent circuit and single outlet must be used.

 

If  electrical  circuit  capacity  is  not  enough  or  defect  in 
electrical work, it will cause electrical shock fire.

 

 

Use  the  specified  cable  and  connect  tightly  and  clamp 
the  cable  so  that  no  external  force  will  be  acted  on  the 
terminal.

 

If  connection  or  fixing  is  not  perfect,  it  will  cause  heat-up  or 
fire at the connection.

 

 

Wiring routing  must be properly arranged so that  control 
board cover is fixed properly.

 

If  control  board  cover  is  not  fixed  perfectly,  it  will  cause 
heat-up  at  connection  point  of  terminal,  fire  or  electrical 
shock.

 

 

If the supply cord is damaged, it must be replaced by the 
manufacture  or  its  service  agent  or  a  similarly  qualified 
person to avoid a hazard.

 

 

An  all-pole  disconnection  switch  having  a  contact 
separation  of  at  least  3mm  in  all  poles  should  be 
connected in fixed wiring.

 

 

When carrying out piping connection, take care not to let 
air substances go into refrigeration cycle.

 

Otherwise,  it  will  cause  lower  capacity,  abnormal  high 
pressure in the refrigeration cycle.

 

 

Do not modify the length of the power supply cord or use 
of extension cord, and do not share the single outlet with 
other electrical appliances.

 

Otherwise, it will cause fire or electrical shock.

 

 

If the water leaks during installation, ventilate the area 
immediately.

 

 

After completing the installation work, check that the 
water does not leak.

 

 

The cool water  in the  unit  is not lower than 3ºC hot water is 
not higher than 65ºC. Water in the unit must clean, air quality 
must meet to the standard of PH=6.5~7.5.

 

Summary of Contents for KFC-S-2T-250D

Page 1: ...il Unit KFC S 2T 250D KFC S 2T 400D KFC S 2T 500D KFC S 2T 900D KFC SE 2T 250D KFC SE 2T 400D KFC SE 2T 500D KFC SE 2T 900D Thank you very much for purchasing our fan coil unit before using your unit please read this manual carefully and keep it for future reference ...

Page 2: ......

Page 3: ...t of refrigerant leakage Contact the place of purchase for more information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Use the attached accessories parts and specified parts for installation otherwise it will cause the set to fall water leakage electrical shock and fire The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry...

Page 4: ...sary Don t install the air conditioner in the following locations There is petrolatum existing There is salty air surrounding near the coast There is caustic gas the sulfide for example existing in the air near a hot spring The Volt vibrates violently in the factories In buses or cabinets In kitchen where it is full of oil gas There is strong electromagnetic wave existing There are inflammable mat...

Page 5: ... Built in version II VERSION I Fig 2 2 2 The phenomenon is normal that the surface of air conditioning may condense water when the relative larger humidity in room please close the door and window 3 Optimum performance will be achieved within these Supply voltage 220 240V 1ph 50Hz Finned coil type heat exchanger consisting of copper tubes and aluminum fins with connections on the left reversible t...

Page 6: ...ntroller can be only installed in 3 way valve side Information about further risks and unavoidable hazards installation manual for controller DANGER Always switch off the electric power before beginning cleaning or maintenance operations Do not spill water on the unit In versions with casing it is possible to clean the outside of the unit For cleaning use a soft cloth dampened with water and alcoh...

Page 7: ...LATION The units should only be moved and lifted by specialized personnel trained in these operations Check on arrival that the unit has not been damaged during transport and that it is complete with all its parts DANGER Movement of the unit should be performed with care in order to avoid damage to the external structure and to the internal mechanical and electrical components Also make sure that ...

Page 8: ... according to national or local rules in force at the time of installation For installation follow the instructions set out below Remove the external casing in versions I and II unscrewing the screws which secure it to the structure as following indicated Fig 3 2 Version a a b Fig 3 4 b a a Fig 3 3 Mark out the fixing points on the wall or ceiling either by marking through the drillings in the uni...

Page 9: ...e drainage connector on the unit How to turn the coil round from fittings on the left standard to fittings on the right The unit is supplied as standard with connections to the coil on the left It is possible however to turn the coil round so that the connections are on the right The operation of turning the principal and supplementary coils round can be carried out with the unit in situ but it is...

Page 10: ...qualified personnel in compliance with the regulations in effect in the country where the unit is installed The company shall not be held liable for damage to persons or property caused by incorrect electrical connection The power cord type designation is H05RN R or above H07RN F This appliance can be children aged from 8 years and above and persons with reduced physical sensory or mental capabili...

Page 11: ...intake grilles Disconnect the power supply before cleaning and maintenance Use dry cloth to clean the unit Always disconnect the unit from the mains power supply at the main isolator switch before carrying out maintenance work or checks Make sure that no one accidentally supplies power to the machine lock the main switch in the Off position SCHEDULED MAINTENANCE Once a month Check the state of cle...

Page 12: ...t to adhere scrupulously to the following procedures The unit should only be dismantled by a firm authorized for the disposal of scrap machinery The unit is composed of materials considered as secondary raw materials and the following conditions must be observed 1 If the system has antifreeze as an additive it must not be just dumped because it causes pollution It should be collected and suitably ...

Page 13: ...Fig 4 1 46 105 55 140 D Fig 4 2 185 207 Fig 4 3 150 150 Fig 4 4 Table 4 1 VERSION I 150 250 300 400 450 500 600 800 900 A mm 800 800 1000 1000 1200 1200 1500 1500 1500 B mm 584 584 784 784 984 984 1284 1284 1284 C mm 500 500 700 700 900 900 1200 1200 1200 D mm 526 526 726 726 926 926 1226 1226 1226 ...

Page 14: ...46 105 D B Fig 4 6 A C 185 Fig 4 7 Fig 4 8 Table 4 2 VERSION 150 250 300 400 450 500 600 800 900 A mm 550 550 750 750 950 950 1250 1250 1250 B mm 526 526 726 726 926 926 1226 1226 1226 C mm 500 500 700 700 900 900 1200 1200 1200 D mm 500 532 732 732 932 932 1232 1232 1232 ...

Page 15: ...4G M 16mm Power supply 220 240V 1ph 50Hz In the following conditions ambient temperature 27 C D B 19 CW B temperature of inlet water 7 C with t5 C at high speed In the following conditions ambient temperature 20 C temperature of inlet water 70 C with t10 C at high speed The A weighted sound pressure level is below 70dB soundpressurelevelindB A refers to a measurement taken at 1m from the point of ...

Page 16: ...MD15IU 015CW DZ1 16126200A06812 ...

Page 17: ...I O manual 15 ...

Page 18: ......

Page 19: ...I O manual 17 ...

Page 20: ......

Reviews: