5.4 Module setting indications
SECTION 5 - SETTINGS MODULE
1) Definitions of each bit of SW1:
ON
1234
SW1-1 is 0: shutdown compensation
temperature (cooling) is 0°C (factory
default)
SW1-1 is 1: shutdown compensation
temperature (cooling) is 2°C (outlet
air temperature control is invalid)
SW1-2 is 0: AHU control box provides
three fan speeds (factory default)
SW1-2 is 1: only one fan speed
Valid for the
master unit only
ON
1234
Valid for the
master unit only
SW1-3 and SW1-4 are 00: the
number of slave AHU control boxes
connected in parallel is 0 (factory
default); valid for the master unit
ON
1234
Valid for the
master unit only
SW1-3 and SW1-4 are 01: the
number of slave AHU control boxes
connected in parallel is 1
SW1-3 and SW1-4 are 10: the
number of slave AHU control boxes
connected in parallel is 2
SW1-3 and SW1-4 are 11: the
number of slave AHU control boxes
connected in parallel is 3
ON
1234
Valid for the
master unit only
ON
1234
Valid for the
master unit only
ON
1234
Valid for the
master unit only
2) Definitions of each bit of SW2:
ON
1234
SW2-1 is 0: automatic addressing
(factory default)
SW2-1 is 1: clearing AHU control
box address
SW2-2 is 0: no self-check (factory
default)
SW2-2 is 1: self-check
ON
1234
SW2-3 and SW2-4 are 00: master
AHU control box
ON
1234
SW2-3 and SW2-4 are 01: slave
AHU control box 1
SW2-3 and SW2-4 are 10: slave
AHU control box 2
SW2-3 and SW2-4 are 11: slave
AHU control box 3
ON
1234
ON
1234
ON
1234
0 means DIP switch is dialled to “OFF”
1 means DIP switch is dialled to “ON”