 13

 NOTE

The wire diameter and continuous length is under the condition 
that the voltage vibration is within 2%. If the continuous length is 
exceed showing value, choose the wire diameter follow relevant 
regulation.

Indoor unit power supply wiring

Indoor Power Supply 

Circuit Breaker

Manual swtich

Wire Distribution Box

Indoor Unit

Fig. 5-6

 CAUTION

1.  Refrigerant piping system, indoor unit-indoor unit connection 

signal wires and indoor unit-outdoor unit connection singal wire 
are in the same system.

2.  When power cord is parallel with signal wire, please put them 

into separate wire distribution pipes, and leave a proper 
distance.(Reference distance: It is 300mm when current 
capacity of power cord is less than 10A, or 500mm when 50A).

 

z

Please use shield wire as indoor unit/outdoor unit signal wire. 

Indoor/Outdoor unit signal wire wiring

Outdoor Unit

Close end of the connection shielded wire

Indoor/Outdoor 

Unit Signal Wire

(open)

In broken line table, users can purchase the wire 

controller when necessary

.

 

Fig. 5-7

         

6.  TEST RUNNING

Operate according to “gist for test running” on the electric control box 
cover.

CAUTION

 

z

Test running can not start until the outdoor unit has been 

connected to the power for 12hr. 

 

z

Test running can not start until all the valves are affirmed open.

 

z

Never make the forced running. (Or the protector sits back, 

danger will occur.)

7.  PRECAUTIONS ON 

REFRIGERANT LEAKAGE

This air conditioner(A/C) adopts inncouous and nonflammable 
refrigerant. The locating room of the A/C should big engough that any 
refrigerant leakage is unable to reach critical thickness. So certain 
esssential action can be taken on time.

 

z

Critical thickness------the Max. thickness of Freon without any harm 

to person.

 

z

Refrigerant critical thickness: 0.44[kg/m³] for R410A.

Confirm the critical thickness through follow steps, and take 
necessary actions.

1.  Calculate the sum of the charge volume (A[kg]) Total 

Refrigerant volume of 10HP=factory refrigerant  
superaddition

2.  Calculate the indoor cubage (B[m³]) (as the minimum cubage.
3.  Calculate the refrigerant thickness

Counter measure against over high thickness

1.  Installmechanicalventilator to reduce the refrigerant thickness 

under critical level. (ventilate regularly)

2.  Install leak alarm facility related to mechanical ventilator if you 

can not regularly ventilate.

b. Leak alarm related to mechanical ventilator

A. Ventilation 

    peristome 

(Leak hunting siren should be installed in 

places easily keep refrigerant) 

Indoor unit

Outdoor unit

Indoor unit

Room full of leak refrigerant

(All refrigerant has run up)

Fig. 7-1

Summary of Contents for Mini Amazon 3 KMF-80 DVN4

Page 1: ...hasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Mini Amazon III KMF 80 DVN4 KMF 100 DVN4 KMF 120 DVN4 KMF 140 DVN4 KMF 1...

Page 2: ...nection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the nationa...

Page 3: ...2kW 2 8 Network matching wires 2 9 Connecting pipe 16kW 1 10 L shaped pipe 14kW 1 NOTE z Check if any accessory in the above figure is missing All the accessories must be kept properly z All the fitti...

Page 4: ...e may be caused There is combustible gas leakage There is much oil including engine oil ingredient There is salty air surrounding near the coast There is caustic gas the sulfide for example existing i...

Page 5: ...let surface Air inlet surface Maintenance cable and pipeline surface 2000 500 3000 3000 300 600 2000 300 3 3 Moving and installation Since the gravity center of the unit is not at its physical center...

Page 6: ...utlet plate The method of the out pipe in the same way of the back out pipe Undersurface outlet pipe the knock out should from inside to outside and then piping and wiring through this Pay attention t...

Page 7: ...5 9 9 5 KCMI 112 160 A 230 19 1 9 5 KCMI 112 4 5 Confirmation for the diameters of outdoor unit connecting pipes R410A outdoor unit connecting pipes diameters Table 4 4 Total capa ctiy of The outdoor...

Page 8: ...on please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m z The main pipes of indoor unit and the indoor unit branch pipe components The downstream inner units of...

Page 9: ...Unit Outdoor Unit Drop Height H Outdoor Unit up 10m 8kW 25m 10 12kW 30m 14 16kW Outdoor Unit Down 10m 8kW 20m 10 12kW 20m 14 16kW Indoor Unit to Indoor Unit Drop Heihgt H 8m Note When the total equiv...

Page 10: ...of the vacuum gauge rises If the reading rises there is residual water or gas leakage in the system The leakage must be checked and solved and the test should be performed again z Water may enter int...

Page 11: ...98 198 198 198 Max V 264 264 264 264 264 MCA 21 25 28 75 35 40 40 TOCA 18 1A 24A 29A 33A 33A MFA 25 32 40 40 40 Compressor MSC Soft star Soft star Soft star Soft star Soft star RLA 9 45 9 45 15 5 15 5...

Page 12: ...for 8kW and reserved digital multimeter interface for 10kW 12kW 14kW and 16kW The arrangement of OAE XYE and PQE depends on the unit Note The wired controller and centralized controller in the dashed...

Page 13: ...le 5 3 Rated current of appliance A Nominal cross sectional area mm Flexible cords Cable for fixed wiring 3 0 5 and 0 75 1 to 2 5 3 and 6 0 75 and 1 1 to 2 5 6 and 10 1 and 1 5 1 to 2 5 10 and 16 1 5...

Page 14: ...connected to the power for 12hr z Test running can not start until all the valves are affirmed open z Never make the forced running Or the protector sits back danger will occur 7 PRECAUTIONS ON REFRIG...

Page 15: ...r equipment that contains fluorinated greenhouse gases in quantities of 50 tonnes of CO2 equivalent or more but of less than 500 tonnes of CO2 equipment at least every six months or where a leakage de...

Page 16: ......

Reviews: