background image

03

– Refrigerating pipe or components are

installed in a position where they are unlikely

to be exposed to any substances which may

corrode refrigerant containing components,

unless the components are constructed of

materials that are inherently resistant to

corrosion or are suitably protected against

corrosion.

Repair and maintenance of electrical 

components shall include initial safety 

checks and component inspection 

procedures. If a fault exists that could 

compromise safety, then no electrical 

supply shall be connected to the circuit 

until the fault has been dealt with 

satisfactorily. If the fault cannot be 

corrected immediately but it is necessary to 

continue operation, an adequate temporary 

solution shall be used. This shall be 

reported to the owner of the equipment so 

that all parties are advised. Initial safety 

checks shall include:

– That capacitors are discharged: this shall be

done in a safe manner to avoid the possibility

of sparking;

– That no live electrical components and wiring

are exposed while charging, recovering or

purging the system;

– That there is continuity of grounding.

When repairing sealed components, all 

electrical supplies shall be disconnected 

from the equipment being worked upon 

prior to any removal of sealed covers, etc. 

If it is absolutely necessary to have an 

electrical supply to the equipment during 

servicing, then a permanently operating 

form of leak detection shall be installed at 

the most critical point to warn of a 

potentially hazardous situation.

Particular attention shall be paid to the 

following to ensure that by working on 

electrical components, the casing is not 

altered in such a way that the level of 

protection is affected. This shall include 

damage to cables, an excessive amount of 

connections, terminals not made to their 

original specification, damage to seals, 

incorrect fitting of glands, etc.

Ensure that the apparatus is mounted 

securely.

Ensure that seals or sealing materials have 

not degraded to the point that they no 

longer prevent the ingress of flammable 

materials. Replacement parts shall conform 

with the manufacturer’s specifications.

Do not apply any permanent inductive or 

capacitance loads to the circuit without 

ensuring that this will not exceed the 

permissible voltage and current permitted 

for the equipment in use.

Intrinsically safe components are the only 

types that can be worked on while live in 

the presence of flammable gases. The test 

apparatus shall be at the correct rating.

Replace components only with parts 

specified by the manufacturer. Other parts 

may result in the ignition of refrigerant 

which has leaked into the surroundings.

Check that cabling will not be subject to 

wear, corrosion, excessive pressure, 

vibration, sharp edges or any other adverse 

environmental effects. The check shall also 

take into account the effects of aging or 

continual vibration from sources such as 

compressors or fans.

Under no circumstances shall potential 

sources of ignition be used while searching 

for or detection of refrigerant leaks. A halide 

torch (or any other detector using a naked 

flame) shall not be used.

Electronic leak detectors may be used to 

detect refrigerant leaks but, in the case of 

flammable refrigerants, the sensitivity may 

not be adequate, or may need re-calibration. 

(Detection equipment shall be calibrated in 

a refrigerant-free area.) Ensure that the 

detector is not a potential source of ignition 

and is suitable for the refrigerant used. Leak 

detection equipment shall be set at a 

percentage of the LFL of the refrigerant and 

shall be calibrated for the refrigerant 

employed, and the appropriate percentage 

of gas (25 % maximum) is confirmed.

If a leak is suspected, all naked flames shall 

be removed/extinguished.

If a leakage of refrigerant which requires 

brazing is found, all of the refrigerant shall 

be recovered from the system, or isolated 

(by means of shut off valves) in a part of the 

system remote from the leak.

When opening the refrigerant circuit to 

make repairs – or for any other purpose – 

conventional  procedures  shall  be used. 

However, for flammable refrigerants it is 

important that best practice is followed 

since flammability is a consideration. The 

following procedure shall be followed:

– Remove refrigerant;

– Purge the circuit with inert gas;

– Evacuate;

– Purge with inert gas;

– Open the circuit by cutting or brazing.

The refrigerant charge shall be recovered 

into the correct recovery cylinders. The 

system shall be “flushed” with OFN to 

render the unit safe. This process may need 

to be repeated several times. Do not use 

compressed air or oxygen for this task.

Flushing shall be achieved by breaking the 

vacuum in the system with OFN and 

continuing to fill until a working pressure is 

achieved, then venting to the surroundings, 

and finally pulling down to a vacuum. This 

process shall be repeated until no 

refrigerant is within the system. When the 

final OFN charge is used, the system shall 

be vented down to atmospheric pressure to 

enable work to take place. This operation is 

absolutely vital if brazing operations on the 

pipework are to take place.

Ensure that the outlet for the vacuum pump 

is not close to any ignition sources and 

there is ventilation available.

Summary of Contents for Mini Amazon KMF-180 DTR6

Page 1: ...ng your air conditioner please read this manual carefully and retain it for future reference The figures shown in this manual are for reference purposes only and may be slightly different from the act...

Page 2: ...6 35 OUTDOOR UNIT INSTALLATION ELECTRICAL WIRING 46 8 9 25 1 2 16 17 19 01 48 COMMISSIONING CONFIGURATION PRECAUTIONS ON REFRIGERANT LEAKAGE 10 49 TURN OVER TO CUSTOMER 11 50 TECHNICAL DATA INSTALLATI...

Page 3: ...12 The figures in this manual are for explanation purposes only They may be slightly different from the air conditioner you purchased depending on the model The actual shape shall prevail Refrigerant...

Page 4: ...e the following instructions must be followed Ignoring these instructions may cause harm or damage The safety precautions listed here are divided into the following types They are quite important so b...

Page 5: ...ng the refrigerating system comply with the following precautions prior to conducting work on the system shall be undertaken according to controlled procedures so as to minimize the risk of the presen...

Page 6: ...ts only with parts specified by the manufacturer Other parts may result in the ignition of refrigerant which has leaked into the surroundings Check that cabling will not be subject to wear corrosion e...

Page 7: ...en confirmed as complying to corresponding partial unit requirements of this International Standard Ensure that contamination of different refrigerants does not occur when using charging equipment Hos...

Page 8: ...ditioner when using a room fumigation type insecticide Failure to observe this precaution could cause the chemicals to become deposited in the unit which could endanger the health of those who are hyp...

Page 9: ...ments 1 3 1 2 Piping installation requirements Low temperature solder alloys such as lead tin alloys are not acceptable for pipe connections Reusable mechanical connectors and flared joints are not al...

Page 10: ...hall be protected or enclosed to avoid damage Equipment pipes in the occupied space in question must be installed in such a way that it is protected against accidental damage The system uses R32 refri...

Page 11: ...for systems needing additional refrigerant charge and which will limit room area strategy Similarly the total amount of refrigerant in the system shall be less than or equal to the maximum refrigerant...

Page 12: ...evel opening The opening shall not be less than 0 0123 m2 Anvmin The area of any openings above 300 mm from the floor shall not be considered in determining compliance with Anvmin At least 50 of the o...

Page 13: ...2 00 4 00 6 00 8 00 10 00 12 00 Minimum room area Amin m2 a Installation height 1 b Installation height 2 c With incorporated circulation airflow for the installation height 1 d With incorporated circ...

Page 14: ...2 12 7 626 9 321 12 12 7 695 9 405 12 12 7 763 9 489 12 12 7 831 9 571 12 12 7 898 9 654 12 12 7 965 9 735 12 12 8 031 9 816 12 12 8 097 9 896 12 12 8 162 9 975 12 12 8 226 10 054 12 12 8 29 10 133 12...

Page 15: ...ight At least one alarm device shall be installed inside each occupied space For the occupancy listed below the alarm system shall also warn at a supervised location such as the night porter s locatio...

Page 16: ...ound floor b The IDU installation height is not less than 2 2 m while A is 14m2 and on the lowest underground floor c The refrigerant charge limitation is on the lowest underground floor while A is 14...

Page 17: ...arge Mmax in the system from the above room area limitations 2 The maximum refrigerant charge Mmax with air duct system or additional measures such as areas with mechanical ventilation 3 12 kg from th...

Page 18: ...the smallest room meets the requirements Calculate the total refrigerant charging amount Mc according to section 5 8 1 Check the corresponding table to get the maximum refrigerant charge Mmax Yes 1 S...

Page 19: ...may be triggered and the air conditioner may malfunction When the unit operates in cooling mode in a relatively humid environment relative humidity higher than 80 condensation may occur on the surface...

Page 20: ...in the following circumstances Cooling Heating Mishandling in operation When the breaker was broken do not use any unspecified breaker or other wire to replace the original breaker The use of electri...

Page 21: ...n it accidentally leaks and comes into contact with flammable substances generated by existing heaters and burning devices in the room Qualified maintenance personnel must verify that the point of lea...

Page 22: ...r to shade the unit from sunshine Reduce heat source AC cooling capacity is reduced normal Check for leakage and correctly recharge refrigerant Causes Power failure Power breaker is off Batteries of t...

Page 23: ...cated on the display When the set time is reached the air conditioner will automatically start and the appropriate indicator will go off Check whether the signal transmitter of the remote controller i...

Page 24: ...T4 error open short Refrigerant leakage sensor error Plate heat exchanger outlet temperature sensor T6B error open short Outdoor heat exchanger temperature sensor T3 error open short Inverter module...

Page 25: ...Technology barrier U02 U12 U21 U31 U32 U33 U34 U35 U37 U3b U3C U41 U3A U38 Compressor high DC bus current protection 1P32 protection occurs 3 times in 100 minutes High AC voltage protection Low AC vol...

Page 26: ...exceeds the upper limit in Cooling mode Outdoor ambient temperature exceeds the lower limit in Cooling mode Refrigerant judgment no result Refrigerant quantity judgment Significantly excessive Refrige...

Page 27: ...em switches over to heating operation after defrost operation moisture generated by defrosting becomes steam and is exhausted A continuous low shah sound is heard when the system is in cooling operati...

Page 28: ...or a similarly qualified person in order to avoid creating a hazard An all pole disconnection switch which has a contact separation of at least 3 mm in all poles should be connected using fixed wirin...

Page 29: ...es water pipes lightning rods or ground wires for telephone cables Conform to the regulations of the local electric company when wiring the power supply Inappropriate grounding may cause electric shoc...

Page 30: ...to low speed The heating capacity of the system decreases as the ambient outdoor temperature decreases In areas where the design heating temperature of the air conditioner is 5 C and the unit needs t...

Page 31: ...ry of a building ensure normal fan operation by using a duct or a wind shield Figure 4 1 Strong wind Strong wind 4 1 2 Installation space Unit mm B A G Figure 4 2 D C I H F E Table 4 1 unit mm Model A...

Page 32: ...uality of the installation seal The piping and other pressure vessels must comply with the applicable laws and be suitable for use with the refrigerant Use only phosphoric acid deoxidized seamless cop...

Page 33: ...HN 01D Gas pipe Liquid pipe 15 9 15 9 19 1 9 52 9 52 9 52 A 63 63 A 160 160 A 280 Branch joint kit Table 4 6 Table 4 7 Indoor unit auxiliary pipe a f Indoor unit capacity 100 W Indoor unit pipe size m...

Page 34: ...6 kW Referring to Table 4 6 the gas and liquid pipe size of L2 are 12 7 and 6 35 respectively and the branch joint B is FQZHN 01D Similarly the pipe size of L3 is 15 9 and 9 52 the pipe size of L3 and...

Page 35: ...ng provided on site Gas side piping provided on site Liquid side piping provided on site Liquid side piping provided on site Liquid side piping provided on site Side outlet connection mode Outlet pipi...

Page 36: ...The leakage must be checked and solved and the test should be performed again Under no circumstances shall potential sources of ignition be used to search for or detect refrigerant leaks A halide tor...

Page 37: ...The total refrigerant charge of the system including factory charge and additional charge must not exceed the maximum design refrigerant charge of 12 kg WARNING Make sure all connected indoor units ha...

Page 38: ...units the maximum allowable voltage range variation between phases is 2 3 Select a circuit breaker that has a contact separation in all poles not less than 3 mm providing full disconnection where MFA...

Page 39: ...the communication terminal block Otherwise the whole system may fail You must first connect the earth line note that you should use only the yellow green wire to connect to the earth and you must turn...

Page 40: ...tion mode of IDU and ODU Table 6 3 communication mode X Y E P Q E M1 M2 O A H1 H2 Controller PQE IDU Comm HyperLink IDU Comm Digital PowerMeter Communication terminal Figure 6 5 6 3 Connecting the Com...

Page 41: ...55014 1 and EN 55014 2 The communication line must be shielded wire Figure 6 6 Figure 6 7 HyperLink M1 M2 communication Keep the power on off for all IDUs Do not connect the HyperLink M1 M2 communicat...

Page 42: ...are optional accessories Please contact the local dealer for purchase if needed Applicable standards EN 55014 1 and EN 55014 2 The communication line must be shielded wire Digital Power Meter O A Refr...

Page 43: ...Function of buttons SW3 to SW6 7 2 3 Menu mode Outdoor unit state Parameters displayed on DSP1 Parameters displayed on DSP2 Standby Unit s address The number of indoor units in communication with the...

Page 44: ...unit address Automatic priority mode Cooling priority mode VIP indoor unit voting priority mode In response to heating mode only In response to cooling mode only Heating priority mode Change over Voti...

Page 45: ...and outdoor unit 40m level difference between indoor unit and outdoor unit 50m level difference between indoor unit and outdoor unit Normal High sensible heat mode Low temperature mode Network address...

Page 46: ...Condensation temperature setting Kc0 51 Non stop compressor defrosting Stop compressor defrosting Self cleaning unavailable Self cleaning available Refrigerant shut off device unavailable Refrigerant...

Page 47: ...VC position Reserved High pressure of unit Low pressure of unit Quantity of online IDUs Quantity of running IDUs 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 3...

Page 48: ...eserved 3 D2 Reserved 4 E1 Evaporator 5 F1 Reserved 6 F2 Reserved 0 Not in special mode 1 Oil return 2 Defrost 3 Startup 4 Stop 5 Quick check 6 Self cleaning 0 5 5 represents the most silent 0 0Pa 1 1...

Page 49: ...the relevant regulations make sure the field wiring is based on the instructions described in section 6 2 and 6 3 on connecting wires Earth line Make sure the earth line is connected correctly and th...

Page 50: ...n If the IDUS and ODU are connected by M1M2 communication please set the 4th digit of the ODU digital display to 2 Once the communication protocol has been set short press the OK button to confirm and...

Page 51: ...nterface should be connected to facilitate the operations of the indoor unit Please refer to the installation manual of the indoor unit for more details INFORMATION i Refer to the installation manual...

Page 52: ...three months or where a leakage detection system is installed at least every six months 4 Non hermetically sealed equipment charged with fluorinated greenhouse gases shall only be sold to the end use...

Page 53: ...rator 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Legend Heat exchanger pipe temperature sensor Outdoor ambient temperature sensor Liquid pipe temperature sensor Plate heat exchanger outlet temperature sensor...

Page 54: ...1 12 13 14 15 EXVA O S INV1 T7C1 GLQ1 GLQ4 ACC PL T71 EXVC T5 GLQ2 T6B TL ST1 T8 T3 GLQ3 Liquid Stop Valve Gas Stop Valve DXF1 PH T4 HPS M 2 4 5 6 7 8 9 10 11 12 13 14 15 3 1 Legend Heat exchanger pip...

Page 55: ...52 11 2 Fan Performance 0 5 10 15 20 25 30 35 40 45 4500 5000 5500 6000 6500 External static pressure Pa Air flow m3 h 0Pa 10Pa 5500 rated 20Pa 30Pa 35Pa 18kW unit fan performance Figure 11 9...

Page 56: ...Tj 25 C Tj 20 C Off mode Thermosat off mode Crankcase heater mode Standby mode PCK PSB Pdc Pdc Pdc Pdc 17 50 12 63 8 15 4 41 kW kW kW kW kW kW kW kW Tj 35 C Tj 30 C Tj 25 C Tj 20 C EERd EERd EERd EER...

Page 57: ...C COPd COPd COPd COPd 2 77 4 64 6 68 9 33 Information requirements for heat pumps Tbiv bivalent temperature Pdh 11 00 kW kW Pdh Tbiv 11 00 2 34 2 34 TOL operation temperature Tbiv bivalent temperatur...

Page 58: ...55...

Page 59: ...16127000004490 V D...

Page 60: ......

Reviews: