TABLE 1 – ELECTRICAL RATINGS
Model
Input
Voltage
(VAC)
Max. AC
Current
(ARMS)
Output Voltage
(VDC)
Max. DC Output
Current (ADC)
Max.
HP, (KW)
KBPC-240D
115
15.0
0 – 90
10.2
1, (.75)
230
15.0
0 – 180
10.2
2, (1.5)
230
15.0
0 – 90
10.2
1, (.75)
TABLE 2 – GENERAL PERFORMANCE SPECIFICATIONS
Parameter
Specification
Factory
Setting
AC Line Input Voltage (VAC ±10%,50/60 Hz)
AC Line Frequency (Hz), # of Phases
Arm Voltage Range at 115VAC Line (VDC)
Arm Voltage Range at 230VAC Line (VDC)
Field Voltage at 115VAC Line (VDC)
Field Voltage at 230VAC Line (VDC)
Horsepower Range at 115 VAC HP, (KW)
Horsepower Range at 230 VAC HP, (KW)
Ambient Temperature Range (
ºC)
Speed Range (Ratio)
Arm Feedback Load Regulation (% Base Speed)
Tach Feedback Load Regulation (% Set Speed)
Line Regulation (% Base Speed)
Current Ranges (ADC)
ACCEL and DECEL Ranges (Sec.)
MIN Speed Range (% Base Speed)
MAX Speed Range (% Base Speed)
IR Comp Range at 115VAC Line (VDC)
IR Comp Range at 230VAC Line (VDC)
CL Range (% Range Setting)
Timed CL Range (Sec.)
Voltage Following Linearity (% Base Speed)
115 or 230
50/60, 1
0 – 90
0 – 180, 0 – 90
100/50
200/100
1/50 – 1, (.015 – .75)
1/25 – 2, (.03 – 1.5)
0 – 50
50:1
±1
±1
±0.5
2.5, 5.0, 7.5, 10
0.1 – 15
0 – 30
60 – 140
0 – 15
0 – 30
0 – 200
0.5 – 15
±0.5
230
—
—
0 – 180
—
—
—
—
—
—
—
—
—
10
1
0
100
4
8
150
7
—
II.
SETTING SELECTABLE JUMPERS.
The KBPC-240D has customer selectable jumpers which must be set before the control can
be used. Bold indicates factory setting. See fig. 1, page 3 for location of jumpers.
A. Control Mode –
Speed
(SPD)
or Torque (TRQ). Note: Factory
setting for J1 is Speed mode. When Jumper J1 is placed in the
"SPD" position the drive will control motor speed as a linear
function of the main potentiometer rotation, or analog voltage
input. The range of output speed can be adjusted with the MIN
and MAX trimpots. The motor will maintain the preset speed as long as the maximum
load does not exceed the current limit set point. If the motor load exceeds the current limit
setting, the Overload LED will turn on and the motor will stall.
SPD
TRQ