background image

10

FIG. 6 – AC LINE AND ARMATURE CONNECTION

C. Field 

(For Shunt Wound

motors 

only

) –  Do not

use F+ and F- terminals for any
other motor type.  Connect
motor shunt field to terminals
F+ and F- for 90VDC motors
with 100VDC fields and
180VDC motors with 200VDC
fields.  For motors with half
voltage fields, 90VDC motors
with 50VDC fields and 180VDC
motors with 100 VDC fields,
connect field to terminals F+ and L1.  See table 7 for
summary of Field Connections.

CAUTION – Shunt-Wound motors may be damaged if field remains connected
without motor rotating for an extended period of time.

FIG. 7A – FULL VOLTAGE FIELD

FIG 7B – HALF VOLTAGE FIELD

TABLE 7 – FIELD CONNECTIONS (Shunt Wound Motors Only)

AC Line Voltage (VAC)

Motor Voltage

Field Voltage (VDC)

Field Connection

115

90

100

F+, F-

115

90

50

F+, L1

230

180

200

F+, F-

230

180

100

F+, L1

230

90*

100

F+, L1

*Step down operation (see sec. III C, p. 6).

D. Ground

 – Be sure to ground (earth) the control via green screw located on chassis.

E. Main Speed Potentiometer

 – The main speed potentiometer can be connected in several

ways using terminals "10," "11," "12," "13." ( A 5K ohm potentiometer is supplied with
control.  A 10K potentiometer can also be used.) 

[WARNING!  Terminals “10,” “11,”

“12" and “13" are not isolated from AC line.  Do not ground (earth).]

i.

Unidirectional operation only – Connect potentiometer to terminals "10," "12," "13" for
forward direction.  (To operate in reverse direction, connect to "11," "12," "13.")

ii.

Bidirectional operation using reversing contacts – Connect to terminals "10," "11,"
"12," "13" as per fig. 8, p. 11.

iii. Bidirectional operation with potentiometer – Connect potentiometer to terminals "10,"

"11," "12" as per fig. 8, p. 11.

Summary of Contents for PENTA KB POWER KBRG-225D

Page 1: ...5 TB1 12 9 7 8 10 11 13 J3 F1 EARTH T1 GND DB ACCEL ACCEL REV FWD RESP SPD MAX CL CL COMP IR REV FWD TCL J8 NLT S LT OFFSET R33 EN FWD REV EN ON PWR CL See Safety Warning on Page 2 The information con...

Page 2: ...on 8 7 Field Connections 10 8 Control State vs Relay Contact State 12 9 Armature Fuse Chart 13 10 Current Limit Timer Settings 15 11 Parts List Logic Board 16 17 12 Parts List Power Board 19 FIGURES 1...

Page 3: ...ctory set for speed control operation SPD For torque control set J7 to TRQ position Note J8 must be set to the S LT position for speed control operation 3 MOTOR CURRENT Jumper J2 is factory set for 15...

Page 4: ...Inhibit are not isolated from AC line Be sure to follow all instructions carefully Fire and or electrocution can result due to improper use of this product This product complies with all CE directive...

Page 5: ...3 FIG 1 CONTROL LAYOUT Illustrates Factory Setting of Jumpers and Approximate Trimpot Settings...

Page 6: ...of the mode selected Set jumper J7 to SPD for speed control or to TRQ for torque control See fig 1 p 3 A Speed Control Mode When jumper J7 is set to the SPD position the KBRG will vary the motor spee...

Page 7: ...er roll diameter changes The S LT torque characteristics are shown in fig 2A FIG 2A LINEAR TORQUE CURVE In the NLT position only torque not speed is varied by the input signal The motor output torque...

Page 8: ...utput current is set to 150 of the J2 position which may be readjusted using the FWD CL and REV CL trimpots Note On Model KBRG 240D position 10A is factory setting TABLE 4 JUMPER J2 POSITION vs MOTOR...

Page 9: ...RT may be used as follows i Install resistor in series with either tach generator lead ii Place J4 in 7V position iii The value of RT is calculated as follows RT 5 4 x Vt x S 68 000 VT Tach voltage i...

Page 10: ...suitable for the KBRG 240D at full rating and a 12 x24 x36 enclosure is suitable for the KBRG 225D at full rating Smaller enclosures may be used if full rating is not required V WIRING Warning Read S...

Page 11: ...LINE FUSE FUSE 2 1 3 4 6 5 12 9 7 8 10 11 13 F1 T1 R69 NOTE CONTROL SHOWN ABOVE IS MODEL KBRG 225D 10 00 203 20 254 00 8 00 25 40 7 62 1 00 0 30 DWG C3900 1 00096 180 34 7 70 7 10 195 58 3 440 87 4 4...

Page 12: ...Voltage Field Voltage VDC Field Connection 115 90 100 F F 115 90 50 F L1 230 180 200 F F 230 180 100 F L1 230 90 100 F L1 Step down operation see sec III C p 6 D Ground Be sure to ground earth the con...

Page 13: ...is in ENABLE state When terminals 8 and 9 are open control is in INHIBIT state See fig 9B IMPORTANT If Enable is not used a jumper must be installed between terminals 8 and 9 or control will not opera...

Page 14: ...des require that each ungrounded conductor contain fusing Separate branch circuit fusing may be required Check local electrical codes 2 Armature Fuse An armature fuse F2 is also provided with a rating...

Page 15: ...ment of trimpots in order to tailor control to exact requirements Readjust trimpots as follows A Forward Acceleration FWD ACCEL and Reverse Acceleration REV ACCEL The FWD ACCEL trimpot determines the...

Page 16: ...ween forward and reverse Adjust deadband trimpot CW until the instability disappears Oscillation may also occur due to response setting See section VIII G p 15 D Forward Current Limit FWD CL and Rever...

Page 17: ...If response is made too fast unstable operation may result H Timed Current Limit TCL Trimpot Trimpot is functional only when control is wired for 3 wire Start Stop and J6 is in the TCL position The TC...

Page 18: ...ee expressed or implied and we are not responsible for any expense including installation and removal inconvenience or consequential damage including injury to any person caused by items of our manufa...

Reviews: