Ventilation and air-conditioning
↵
In order to preserve the performance of the air-con-
ditioning unit, clean the heat exchangers after
500 - 600 hours of operation.
㊶
㊷
㊸
Air-conditioning unit
㊶
Heat exchanger
㊷
Condensate pump
㊸
Condensate tray
Page
42
Open the bench part.
㊶
Clean the heat exchanger.
Vacuum it carefully, paying attention not to
damage the fins.
SERVICING THE VENTILATION SYSTEM
⇒
Check all hose connections.
⇒
Remove any kinks in the air hoses. Replace
defective hoses immediately.
The exhaust air hose must not exceed a
maximum length of 6 m if there is no auxiliary
fan installed.
CHECKING THE CONDENSATE PUMP
The condensate pump
㊷
pumps away the
condensation water at timer-controlled intervals.
Check the function of this pump with each tube
replacement.
⇒
Fill some water into the condensate tray
㊸
.
Use a hose and a funnel to do so.
Make sure that the water does not spill over.
⇒
Start a tanning session and then wait for 20
minutes.
⇒
The filling level of the tray must then be below
the pump level.
M a n u a l e o p e r a t i v o
|
megaSun 6700 - 6800 - 6900
51
Summary of Contents for megaSun 6900 alpha deluxe
Page 1: ...MANUALE OPERATIVO...