Commissioning
NOTICE!
Material damage due to non-observance of the
connection conditions or impermissible overvoltage!
Failure to comply with the connection conditions or exceeding the permissible voltage
range may damage or destroy your device.
Before applying the supply voltage to the device, the following points must be
observed:
Voltage and frequency must correspond to the specifications on the type label!
Observe the limit values as described in the technical data!
Observe features of the device
In the building installation, the supply voltage must be provided by a listed
miniature circuit breaker and fuse that meets the requirements of IEC 60947-1 and
IEC 60947-3!
The miniature circuit breaker must
- be easily accessible to the user and installed close to the device.
- Label for the respective device.
Do not take the supply voltage at the voltage transformers.
Provide a fuse for the neutral conductor if the neutral connection
of the source is not earthed