4.3.3 Wizard setting Net type
Basic settings / network connection
The net type form cannot
be edited if the PQ standard
EN50160-LVIT or EN50160-MV/HV
is selected!
For more information about the network
connection, see Chapter Hardware connec-
tion
Net type:
Entering the grid type „3-conductor grid“,
„4-conductor grid“ and/or „4 x 1 conductor
grid“ will determine how the Power Quality
events are recorded.
Switch between 3-conductor and
4-conductor grids.
– In a 3-conductor grid, all events are
calculated from the lineline voltages.
– In a 4-conductor grid and/or a 4 x 1
conductor grid all Power Quality events are
determined from the line-earth voltages.
4.3.4 Wizard setting Net frequency
Grid frequency
Setting grid frequency to 50 Hz or 60 Hz.
Setup wizard
Net type
4 cond, 3 phase
Setup wizard
Net frequency [HZ]
50 Hz
Parameterization