5.5
Current Inputs
Current Inputs
Channels
I1, I2, I3, IN/4
Electrical safety
300 V CAT III
Input type
Differential, isolated
Impedance
≤ 4 mΩ
Nominal input current I
N
5 A
A
C
Full scale range (FSR)
10 A
AC
Overload capacity permanent
≤ 10s
≤ 1s
20 A
100 A
500 A
Waveform
AC, any
Maximaler Crest-Faktor @ I
N
4
Bandwith
25 Hz...20 kHz
Residual current monitor (RCM) – from firmware version 2.2
Nominal current I
N
30 mA
Impedance
4 Ω
Overload capacity
5 A (1 seconds)
Resolution
24 Bit-ADC
5.6
Binary inputs
Binary inputs (BI)
8 binary inputs
Range
0 V..250 V
AC
/ V
DC
H – Level
L – Level
> 35 V
< 20 V
Signal frequency
DC ... 70 Hz
Input resistance
> 100 kΩ
Electrical isolation
Optocoupler, electrically isolated
Electrical safety DIN EN 61010
300 V
Technical data