28592_EDEK
ZA0044-0224-1_EN
37
Technical data
Continued: Table 5.10 Connection / terminal
Terminal
strip no.
Desig-
nation
Function
Terminal
no.
cross section
[mm²]
Stripping
length
[mm]
Torque
[Nm]
X2
l1
S1 (K)
61
ring terminals
1,5 – 4 mm
2
0,5 – 0,8
S2 (L)
62
l2
S1 (K)
63
0,5 – 0,8
S2 (L)
64
l3
S1 (K)
65
0,5 – 0,8
S2 (L)
66
l4
S1 (K)
67
0,5 – 0,8
S2 (L)
68
X3
I5
+
91
solid: 0,2 – 1,5
flexible:
0,2 – 2,5
10
0,5 – 0,6
–
92
10
0,5 – 0,6
Connection cables to be used
- Provide safety devices (fuse) for CAT II.
- Do not mix touchable and dangerous active circuits.
- Connection cables must be designed for a temperature of at
least 62°C.