Q.5.62 February 2021
Page 25
© Copyright 2021 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 EdgeManager
(KE2-EM35)
Overview, Installation, and Setup Instructions
Appendix A
Serial (Modbus) Configuration -
First Installation of Serial (Modbus) Devices on KE2-EM35
RECOMMENDATIONS:
Daisy chain the connection only.
Maximum 1,000ft. total cable length.
CAT-5/CAT-6 are the most cost effective solutions that meet
Serial (Modbus) specifications. Use 24 gauge or better.
STEP 1- Daisy chain connections on controllers
(See Appendix B).
STEP 2 - Finish wiring controllers to pluggable connector.
Do not plug into KE2-EM35 or power on KE2-EM35
STEP 3 - Power on controllers.
STEP 4 -
KE2 Adaptive Control & KE2 Low Temp
Change Serial (Modbus) address on each controller
Each controller’s Serial (Modbus) address must be
unique. Available addresses are 2-247.
Press and hold the
button to access the Advanced
menu.
t5 is displayed
5
t
Then, use the
arrow until you see Adr (Address)
r
d
A
Press
and current address is displayed (default =1)
1
Change the address
by pressing the
or
arrow to
change the value. Use the
button to move to the next
digit. Again change the value using the
or
arrow. Avail-
able addresses are 2 to 247.
When address is set to the preferred value (Ex. 24), press and
hold
for 3 seconds to save the address.
4
2
Example
The controller will return to the Adr screen when the setting
is saved.
r
d
A
The setting change can be verified by pressing the
button.
To exit, press the
button several times.
STEP 4 -
KE2 Temp
Change Serial (Modbus) address on each controller
Each controller’s Serial (Modbus) address must be unique.
Available addresses are 2 to 247.
Press and hold
to access the Setpoints menu.
t5 is displayed
5
t
Then, use the
arrow until you see Adr (Address)
r
d
A
Press
and the current address is displayed (default =1)
Change the address
by pressing the
or
arrow to
change the value. Use the
button to move to the next
digit. Available addresses are 2 to 247.
When address is set to the preferred value (ex. 123), press and
hold
for 3 seconds to save the address.
3
2
1
Example
The controller will return to the Adr screen when the setting
is saved.
r
d
A
The setting change can be verified by pressing the
button.
To exit, press the
button several times.