7.8 Battery Temperature Probe Installation.
NOTE: If the probe is not connected, the UPS will continue to charge the batteries, but not optimize
the DC voltage for temperature.
The MX includes a temperature probe that
connects to one of the (+) post on the batteries.
The (+) at the end of the string or where the total
VDC is measured.
Notice if the probe is not installed, the display will
indicate (CHECK PROBE). This does not mean
that the batteries will not charge. It is only to
maximize the battery voltage during temperature
fluctuations.
Connect to VDC positive on the
end battery string. Or to a
battery surface with an adhesive
20
DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English
20180312
- This manual is for qualified personnel only