SECTION 8
8.1 DBL MX INSTALLATION
NOTE:
The input to the UPS is always Black for Line and White for Neutral. Output
from the UPS is always Red for the Line (Load) and White is for the Neutral. Failure to
follow this, will damage the UPS and Bypass Switch and Void the Warranty.
Before proceeding, the
Bypass
Switch must be installed with the conductors in place and terminated as
indicated in the previous pages. Grounding is very important.
Terminations must be tight and correct.
Always use the
Red Conductor for the Load/Protected side
.
The Black/Line is always used for the Utility side.
Always
Follow
the correct grounding procedures.
The DBL MX is supplied with an AC/ Anderson 6 pole latching and a D/C Anderson 4-Pole latching
connector assembly.
* Both ends, of the A/C harness are exactly the same and reversible.
1) You will notice Black with a Green (PP-30) connector.
2) One latching end is inserted into the 6-Pole Anderson power connector on the UPS.
21
DBL MX-U Series UPS Outdoors 1000-2000W 120V Manual English
20180312
- This manual is for qualified personnel only
To Batteries