KE RT Series UPS 6-10kVA UL 208-220-230-240Vac User Guide English 20180130 This manual is for qualified personnel only
- 28 -
5.4.5
Battery quantity setting
Battery quantity setting – Note: the area marked by the broken-line will be flashing.
Within the battery capacity setting press DOWN or within the bypass voltage upper limit setting press
UP, to go to the battery quantity setting.
•
Use button ENTER/ON to choose the different battery quantity. Battery quantity range is
16
、
18, 20.
•
Press ESC/OFF button to exit the battery quantity setting (save the battery quantity setting)
and goes to battery capacity setting or bypass voltage upper limit setting.
5.4.6
Bypass Volt-Hi setting
Bypass voltage upper limit setting – Note: the area marked by the broken-line will be flashing.
Within the battery quantity setting press DOWN, or within the bypass voltage lower setting press UP,
to go to the bypass upper limit setting.
•
Use button ENTER/ON to set the different bypass voltage upper limit. The bypass voltage
upper limit range is 5%,10%,15%,25%(25% only for 220V output).
•
Press ESC/OFF button to exit the bypass voltage upper limit setting (save the bypass voltage
upper limit setting) and goes to battery quantity setting or bypass voltage lower limit setting.