KE RT Series UPS 6-10kVA UL 208-220-230-240Vac User Guide English 20180130 This manual is for qualified personnel only
- 30 -
5.4.9
Battery Test Setting
The default Setting is “OFF”. When set to “ON”, the battery self-test occurs automatically every 30
days. There are three kinds of Battery Self-test Time, as below.
On1, UPS will transfer to Battery Mode automatically once every 30 days. Self-test Time is 10 seconds.
On2, UPS will transfer to Battery Mode automatically once every 30 days. Self-test Time is 10 minutes.
---
On3, UPS will transfer to Battery Mode automatically once every 30 days. Self-test Time is to the End
of Discharge.