background image

 

 

KE RT Series UPS 6-10kVA UL 208-220-230-240Vac User Guide English 20180130    This manual is for qualified personnel only 

- 16 -

 

4

 

Installation 

4.1

 

Inspecting the UPS 

If any of the equipment received has been damaged during shipment, keep the shipping cartons and 

packing materials in case a return is required and file a claim for shipping damage. If you discover 

damage after acceptance, file a claim for concealed damage. 

 

To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of 

receipt  of  the  equipment;  2)  Send  a  copy  of  the  damage  claim  within  15  days  to  your  service 

representative. 

4.2

 

Unpacking the Cabinet   

CAUTION 

 

Unpacking the cabinet in a low-temperature environment may cause condensation to 
occur in and on the cabinet. Do not install the cabinet until the inside and outside of 

the cabinet are absolutely dry (hazard of electric shock).   

 

The cabinet is heavy. Be careful unpacking and moving the cabinet.   

 
To unpack the cabinet and accessories: 

1.

 Open the outer carton and remove the accessories packaged with the cabinet. 

2.

 Carefully lift the cabinet out of the outer carton. 

3.

 Discard or recycle the packaging in a responsible manner. 

Place the cabinet in a protected area that has adequate airflow and is free of humidity, 

flammable gas, and corrosion. 
 

4.3

 

Installation notes 

Place the UPS in a clean, stable environment, avoid the vibration, dust, humidity, flammable gas and 
liquid, corrosive  objects. To avoid from  high room temperature, a system  of room extractor fans is 
recommended  to  be  installed.  Optional  air  filters  are  available  if  the  UPS  operates  in  a  dusty 
environment. 
 
The environment temperature around the UPS should keep in a range of 0

40

. If the environment 

temperature  exceeds  40

,  the  rated  load  capacity  should  be  reduced  by  12

  per  5

.  The  max 

temperature must not be higher than 50

 
If the UPS is dismantled under low temperature, it might be in a condensing condition. The UPS can't 
be installed unless the internal and external of the equipment is fully dry. Otherwise, there will be in 
danger of electric shock. 
 
Batteries should be  mounted in an environment where the temperature is within the required specs. 
Temperature is a  major factor in  determining battery life and capacity.  In a normal installation, the 
battery temperature is maintained between 15°C and 25°C. Keep batteries away from heat sources or 
main air ventilation area, etc. 
 
Should the equipment not be installed immediately it must be stored so as to protect it against excessive 
humidity and or heat sources. 
 

 

Summary of Contents for RT 10KVA

Page 1: ...ES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK AND C REMINDS YO...

Page 2: ...the parallel system 21 5 Operation 22 5 1 Operation Modes 22 5 2 Turn on off UPS 22 5 2 1 Connecting with Utility 22 5 2 2 Black Cold start procedure 23 5 2 3 Inverter Off 23 5 2 4 Disconnecting with...

Page 3: ...rent protection in accordance with the National Electrical Code NEC ANSI NFPA 70 Output overcurrent protection and disconnect switch must be provided by others To comply with international standards a...

Page 4: ...r And also support for single phase input Digital Control This series UPS is controlled by Digital Signal Processor DSP which increases reliability performance enables self protection and self diagnos...

Page 5: ...80130 This manual is for qualified personnel only 4 3 UPS Module Overview Front View Rear View Side View 1 handles 2 LCD Display 3 PDU 4 EPO 5 Parallel Port 1 6 Intelligent slot 7 Battery Slot 8 Input...

Page 6: ...nglish 20180130 This manual is for qualified personnel only 5 3 1 LCD control panel LCD control panel introduction 1 INVERTER LED 2 BATTERY LED 3 BYPASS LED 4 ALARM LED 5 LCD display 6 UP button 7 DOW...

Page 7: ...nsible manner Place the cabinet in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion 4 3 Installation notes Place the UPS in a clean stable environment avo...

Page 8: ...equals max load at altitude divided by nominal power of the UPS Altitude m 1500 2000 2500 3000 3500 4000 4500 5000 Load coefficient 100 95 90 85 80 75 70 65 4 4 External Protective Devices For safety...

Page 9: ...rotective earth cable Connect each cabinet to the main ground system For Grounding connection follow the shortest route possible WARNING Failure to follow adequate earthing procedures may result in el...

Page 10: ...a positive and negative double battery framework with 16 optional 18 20 pieces in series A neutral cable is retrieved from the joint between the cathode of the 8th 9th 10th and the anode of the 9th 1...

Page 11: ...ing to battery capacity selected All related settings can be done through LCD panel or monitoring software CAUTION Ensure correct polarity battery string series connections I e inter tier and inter bl...

Page 12: ...a ring configuration between UPS modules as shown below The parallel control board is mounted on each UPS module The ring configuration ensure reliability of the control 4 10 Requirement for the para...

Page 13: ...al AC load This is to avoid paralleling of unsynchronized AC sources This interruption is programmable but typically set to be less than an electrical cycle e g less than 15ms 50Hz or less than 13 33m...

Page 14: ...s later the inverter starts INV and output light up CAUTION Wait for approximately 30 seconds before you press the black start key 5 2 3 Inverter Off When the Utility is normal press ESC OFF button fo...

Page 15: ...Voltage Current 04 Bat Voltage Current 05 Temperature PFC Internal temperature and ambient temperature 06 Load Load 07 Bus voltage Bus voltage 08 Software version DSP version of inverter software 09...

Page 16: ...ternal temperature down 8 Bus voltage 9 Software version 5 4 Parameters setting The setting function is controlled by four buttons ENTER ON ESC OFF UP DOWN ENTER goes into the setting page and value a...

Page 17: ...parallel redundancy quantity setting 5 4 2 Output voltage setting Output voltage setting Note the area marked by the broken line will be flashing Within the mode setting press DOWN or within the frequ...

Page 18: ...nd goes to output voltage setting or battery capacity setting Note When powered by inverter it is necessary to turn off the inverter before setting voltage and frequency level 5 4 4 Battery capacity s...

Page 19: ...quantity setting save the battery quantity setting and goes to battery capacity setting or bypass voltage upper limit setting 5 4 6 Bypass Volt Hi setting Bypass voltage upper limit setting Note the a...

Page 20: ...he bypass voltage lower limit setting and goes to bypass upper limit setting or parallel ID setting 5 4 8 Buzzer Mute Setting Buzzers mute setting Note the area marked by the broken line will be flash...

Page 21: ...est occurs automatically every 30 days There are three kinds of Battery Self test Time as below On1 UPS will transfer to Battery Mode automatically once every 30 days Self test Time is 10 seconds On2...

Page 22: ...D setting save the parallel ID setting and goes to bypass lower limit setting or parallel quantity setting NOTE Parallel cable cannot be connected when setting the parallel parameters 5 4 11 Parallel...

Page 23: ...ing Note the area marked by the broken line will be flashing Within the parallel quantity setting press DOWN to go to the parallel redundancy quantity setting Use button ENTER ON to set the parallel r...

Page 24: ...100 linear load input THDV 1 5 100 non liner load input THDV 1 battery Battery number 16 18 20pcs can be set Battery type VRLA Charge model Boost charge or float charge auto switch Charge time Boost c...

Page 25: ...ty IEC62040 1 UL 1778 CSA C22 2 Max input voltage 320Vac 1Hr EMC IEC 62040 2 FCC Part 15 Class B MTBF 250 000Hr 1 1 400 000Hr MTTR 30min Isolation resistance 2M 500Vdc Isolation intension 2820Vdc 3 5m...

Page 26: ...definition USB communication port 1 2 4 3 Definition of Male port Pin 1 VCC Pin 2 D pin 3 D Pin 4 GND Application use UPSilon2000 Power Management software Available functions of the USB Monitor UPS p...

Page 27: ...LED lit 3 Inverter Thyristor short Beep continuously Fault LED lit 4 Inverter Thyristor broken Beep continuously Fault LED lit 5 Bypass Thyristor short Beep continuously Fault LED lit 6 Bypass Thyris...

Page 28: ...nce per second Fault LED blinking 28 Bypass Site Wiring Fault Once per second Fault LED blinking 29 Output Short circuit Once per second Fault LED blinking 30 Rectifier over current Once per second Fa...

Reviews: