- 18 -

 

Power Cables   

The cable design shall comply with the voltages and currents provided in this section.  Follow local 

wiring  codes  and  laws  taking  into  consideration  the  environmental  conditions  (temperature  and 

physical). 

WARNING 

Upon starting, ensure that you are aware of the location and operation of the external 

isolators  which  are  connected  to  the  UPS  input/bypass  supply  of  the  mains 

distribution panel. Check to see if these supplies are electrically isolated. Post any 

necessary warning signs to prevent any inadvertent operation. 

 

For future expansion, it is recommended to install power cable according to the full rated capacity. 

 

UPS 

module

 

Cable Dimension 

AC Input 

(mm

2

AC Output 

(mm

2

DC Input 

(mm

2

Grounding 

(mm

2

6KVA

 

10KVA 

10 

10 

10 

10 

 

CAUTION 

Protective  earth  cable:  Connect  each  cabinet  to  the  main  ground  system.  For 

Grounding connection, follow the shortest route possible. 

 

WARNING 

Failure  to  follow  adequate  earthing  procedures  may  result  in  electromagnetic 

interference or in hazards involving electric shock and fire. 

 

4.5

 

Power cable connections 

Once the equipment has been finally positioned and secured, connect the power cables as described in 

the following procedure. 

 

Verify the UPS is totally isolated from its external power source and also all power isolators of the UPS 

are open. Check to see if they are electrically isolated, and post any necessary warning signs to prevent 

their inadvertent operation. 

 

Select the appropriate power cable (Refer to the table above). 

 

Pay attention to the diameter of the connection terminal of the cable that should be greater than or equal 

to that of the connection poles; 

 

Connect the safety earth and any necessary bonding earth cables to the copper earth screw located on 

the floor of the equipment below the power connections. All cabinets in the UPS must be grounded 

properly. 

 

 

 

 

Summary of Contents for RT 10KVA

Page 1: ...ES WHETHER SPECIAL DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK AND C REMINDS YO...

Page 2: ...the parallel system 21 5 Operation 22 5 1 Operation Modes 22 5 2 Turn on off UPS 22 5 2 1 Connecting with Utility 22 5 2 2 Black Cold start procedure 23 5 2 3 Inverter Off 23 5 2 4 Disconnecting with...

Page 3: ...rent protection in accordance with the National Electrical Code NEC ANSI NFPA 70 Output overcurrent protection and disconnect switch must be provided by others To comply with international standards a...

Page 4: ...r And also support for single phase input Digital Control This series UPS is controlled by Digital Signal Processor DSP which increases reliability performance enables self protection and self diagnos...

Page 5: ...80130 This manual is for qualified personnel only 4 3 UPS Module Overview Front View Rear View Side View 1 handles 2 LCD Display 3 PDU 4 EPO 5 Parallel Port 1 6 Intelligent slot 7 Battery Slot 8 Input...

Page 6: ...nglish 20180130 This manual is for qualified personnel only 5 3 1 LCD control panel LCD control panel introduction 1 INVERTER LED 2 BATTERY LED 3 BYPASS LED 4 ALARM LED 5 LCD display 6 UP button 7 DOW...

Page 7: ...nsible manner Place the cabinet in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion 4 3 Installation notes Place the UPS in a clean stable environment avo...

Page 8: ...equals max load at altitude divided by nominal power of the UPS Altitude m 1500 2000 2500 3000 3500 4000 4500 5000 Load coefficient 100 95 90 85 80 75 70 65 4 4 External Protective Devices For safety...

Page 9: ...rotective earth cable Connect each cabinet to the main ground system For Grounding connection follow the shortest route possible WARNING Failure to follow adequate earthing procedures may result in el...

Page 10: ...a positive and negative double battery framework with 16 optional 18 20 pieces in series A neutral cable is retrieved from the joint between the cathode of the 8th 9th 10th and the anode of the 9th 1...

Page 11: ...ing to battery capacity selected All related settings can be done through LCD panel or monitoring software CAUTION Ensure correct polarity battery string series connections I e inter tier and inter bl...

Page 12: ...a ring configuration between UPS modules as shown below The parallel control board is mounted on each UPS module The ring configuration ensure reliability of the control 4 10 Requirement for the para...

Page 13: ...al AC load This is to avoid paralleling of unsynchronized AC sources This interruption is programmable but typically set to be less than an electrical cycle e g less than 15ms 50Hz or less than 13 33m...

Page 14: ...s later the inverter starts INV and output light up CAUTION Wait for approximately 30 seconds before you press the black start key 5 2 3 Inverter Off When the Utility is normal press ESC OFF button fo...

Page 15: ...Voltage Current 04 Bat Voltage Current 05 Temperature PFC Internal temperature and ambient temperature 06 Load Load 07 Bus voltage Bus voltage 08 Software version DSP version of inverter software 09...

Page 16: ...ternal temperature down 8 Bus voltage 9 Software version 5 4 Parameters setting The setting function is controlled by four buttons ENTER ON ESC OFF UP DOWN ENTER goes into the setting page and value a...

Page 17: ...parallel redundancy quantity setting 5 4 2 Output voltage setting Output voltage setting Note the area marked by the broken line will be flashing Within the mode setting press DOWN or within the frequ...

Page 18: ...nd goes to output voltage setting or battery capacity setting Note When powered by inverter it is necessary to turn off the inverter before setting voltage and frequency level 5 4 4 Battery capacity s...

Page 19: ...quantity setting save the battery quantity setting and goes to battery capacity setting or bypass voltage upper limit setting 5 4 6 Bypass Volt Hi setting Bypass voltage upper limit setting Note the a...

Page 20: ...he bypass voltage lower limit setting and goes to bypass upper limit setting or parallel ID setting 5 4 8 Buzzer Mute Setting Buzzers mute setting Note the area marked by the broken line will be flash...

Page 21: ...est occurs automatically every 30 days There are three kinds of Battery Self test Time as below On1 UPS will transfer to Battery Mode automatically once every 30 days Self test Time is 10 seconds On2...

Page 22: ...D setting save the parallel ID setting and goes to bypass lower limit setting or parallel quantity setting NOTE Parallel cable cannot be connected when setting the parallel parameters 5 4 11 Parallel...

Page 23: ...ing Note the area marked by the broken line will be flashing Within the parallel quantity setting press DOWN to go to the parallel redundancy quantity setting Use button ENTER ON to set the parallel r...

Page 24: ...100 linear load input THDV 1 5 100 non liner load input THDV 1 battery Battery number 16 18 20pcs can be set Battery type VRLA Charge model Boost charge or float charge auto switch Charge time Boost c...

Page 25: ...ty IEC62040 1 UL 1778 CSA C22 2 Max input voltage 320Vac 1Hr EMC IEC 62040 2 FCC Part 15 Class B MTBF 250 000Hr 1 1 400 000Hr MTTR 30min Isolation resistance 2M 500Vdc Isolation intension 2820Vdc 3 5m...

Page 26: ...definition USB communication port 1 2 4 3 Definition of Male port Pin 1 VCC Pin 2 D pin 3 D Pin 4 GND Application use UPSilon2000 Power Management software Available functions of the USB Monitor UPS p...

Page 27: ...LED lit 3 Inverter Thyristor short Beep continuously Fault LED lit 4 Inverter Thyristor broken Beep continuously Fault LED lit 5 Bypass Thyristor short Beep continuously Fault LED lit 6 Bypass Thyris...

Page 28: ...nce per second Fault LED blinking 28 Bypass Site Wiring Fault Once per second Fault LED blinking 29 Output Short circuit Once per second Fault LED blinking 30 Rectifier over current Once per second Fa...

Reviews: