INSTALLATION AND CONNECTION
3.5 Avoid damages due to overheating
• All C6 E22 BOX/PANEL systems are designed for vertical position mounting.
• An inclined installation reduces the thermal convection and the maximum permissi-
ble ambient temperature for C6 E22 BOX/PANEL operation. Please contact KEB for
details. C6 E22 BOX/PANEL may otherwise be damaged and its certifications and
warranty will be void.
• The ambient temperature must be between 0°C and 50°C, as measured 5 cm from
all openings of the system where there is air entrance.
• Provide space around the system for air recirculation and heat exchange.
• Keep at least 5 cm of free space behind (z) and to the sides (x) of the PC cell; above
(y) and below (y) 10cm are needed. Refer to 3.5.1 for a description.
• Make sure that the grids on PC cell for air exchange are free from objects and from
the cables and far from other obstacles to the air flow.
• For example, when the system is installed in cabinets with no air-conditioning, it is
necessary to ensure the exchange of air from outside through at least two openings:
a) An opening should be placed under the PC cell; it must be large enough to
allow the correct air flow from outside.
b) An large enough opening must be positioned above the PC cell, in order to
allow the outflow of the hot air.
c) Of course, it must be checked that the measured ambient temperature (see
above) complies with the required limits.
• Alternatively, it is possible to use lateral openings, subject to the condition that their
vertical dimension is long enough to ensure the required heat exchange.
• When the system is placed in air conditioned cabinets, the conditioning system must
provide the air circulation with proper ventilation.
• When the system is installed in closed cabinets, it is still necessary to ensure that
the maximum ambient temperature is 50°C.
• Mounting angle:
a) The system is intended to be mounted vertically.
b) For inclinations up to 20°, it is necessary to decrease the maximum operating
temperature of 5°C. Therefore, the maximum ambient temperature is 45°C.
c) For other instal-lation modes, contact KEB Automation KG
3.5.1 Checking installation distances
To ensure adequate heat transfer, it is necessary to leave the following open spaces
around the system:
• X direction 5 cm (min.) for each side.
• Y direction 10 cm (min.) for each side.
• Z direction 5 cm (min.).
Mounting the clamps requires a space at least 20 mm on the outer perimeter
of the frame display.
Summary of Contents for C6 E22 BM-RVL
Page 1: ...EMBEDDED IPCS INSTRUCTIONS FOR USE E22 BOX PANEL Original Manual Document 20146638 EN 01 ...
Page 2: ......
Page 11: ...11 List of Figures Figure 89 External connectors 108 Figure 90 Buttons position detail 108 ...
Page 48: ...48 Installationand connection ...
Page 96: ...96 Drawings 7 1 4 C6 E22 PANEL SL S1 12 1 W Figure 75 12 1 Wide dimensions ...
Page 110: ...110 Certificatesandapprovals 8 Certificates and approvals 8 1 EU Declaration of conformity ...
Page 111: ...111 Certificatesandapprovals ...
Page 114: ......