4 | Connection of the control
KEB Automation KG
22
ma_dr_f6-cu-a-inst-20118593_en
Consumer
Current consumption
Control
0.6 A
Power unit
Housing 2 / 3 / 4
0 A
Housing 6
0.6 A
Housing 7 / 8 / 9
1.0 A
Consumer
Brake
Max. 2.0 A
Encoder
Max. 0.5 A
Digital output DO1
Max. 0.1 A
Digital output DO2
Max. 0.1 A
Voltage output 24Vout
Max. 0.1 A
Sum DO safety module
Max. 0.4 A
Tab. 10:
Calculation the current consumption
In order to calculate the input current, the currents of the power unit, control and
other loads must be added together. The actual current required can be used for
the consumers. The maximum current must not be exceeded.
4.2.6.1.2 External supply
Specification external supply
Name
P24Vin, 0V
Terminals
X2A.28 (P24Vin)
X2A.27 (0V)
Voltage
DC 24 V (+20 % / -17 %)
Current consumption
Calculated value up to max. 4.8 A
Connection of the external supply
27
28
+
-
X2A
ACHTUNG! The power-off function is not available if the controller is supplied
externally.
4.2.6.2 Voltage output to supply the inputs
Specification voltage output
Name
24Vout
0V (reference potential)
Terminals
X2A.16 (24Vout)
X2A.27 (0V)
Output current
max. 100 mA (short-circuit proof)
Output voltage
minimum P24Vin - 3V
maximum P24Vin