68
cONNecTION OF THe POWer UNIT
4.2.5 connection of the motor
4.2.5.1 Wiring of the motor
U
V
W
U
V
W
5
6
X1C
X1A
➀
➁
➂
9
10
Control
P A/K
④
Legend
①
KEB COMBIVERT
②
Apply motor cable, shielding on both sides over a large surface on the bare metallic frame or mounting
plate (remove paint if necessary)
③
Three-phase motor
④
Temperature monitoring (optional) =>
Instructions for use „Control circuit“
Figure 22:
Wiring of the motor
4.2.5.2 Terminal block X1A motor connection
Name
Function
cross-section for terminal connection
Tightening
torque
Max. number
of conductors
U
Motor connection
Flexible line with wire-end ferrule with
plastic collars 2.5...10 mm²
For 2 conductors 0.5mm...1.5mm²
For UL flexible line without wire-end
ferrule AWG 26...6
1.5 Nm
13 Ib inch
For IEC: 2
For UL: 1
V
W
Figure 23:
Terminal block X1A motor connection
Summary of Contents for COMBIVERT 10F6 Series
Page 2: ......