cONNecTION OF THe POWer UNIT
4.2.5.5 Motor cable length for parallel operation of motors
The resulting motor cable length for parallel operation of motors, or parallel installation
with multiple cables arises from the following formula:
resulting motor cable length = ∑single line length x √
Number of motor lines
4.2.5.6 Motor cable cross-section
The motor cable cross-section is dependent
• on the characteristic of the output current (e.g. harmonic content)
• on the real effective value of the motor current
• on the line length
• on the type of the used line
• on the ambient conditions such as bundling and temperature
4.2.5.7 Interconnection of the motor
NOTICE
Incorrect behavior of the motor!
►
The connecting-up instructions of the motor manufacturer are al-
ways generally valid!
Protect motor against voltage peaks!
►
Drive converters switch at the output with high dv/dt. Voltage peaks
that endanger the insulation system at the motor can occur espe-
cially in case of long motor cables (>15 m). A motor choke, a dv/
dt-filter or sine-wave filter can be used to protect the motor with
regard to the operating mode.