GB-11
Start-Up Instructions
3.1
Commissioning of
an Asynchronous
Machine with Gearbox
3.
S t a r t - U p
Instructions
The following procedure is recommended for the commissioning of
the KEB COMBIVERT F4-F lift version 3.0 with asynchronous machine
and gearbox:
Adjust the parameters in ascending sequence, as this initiates partial
presettings of the unit. Start with the lift data (LF-parameter). Save
the adjusted data by activating the „Enter key“.
LF.00: Enter password (440)
LF.02: Enter setpoint setting/rotation setting
1 = Binary coded setpoint setting
2 = Input coded setpoint setting
3 = Analog setpoint setting 0...+10V
4 = Analog setpoint setting -10...+10V
LF.04: Check, if the value „0“ is adjusted (asynchronous machine)
LF.20: Enter system speed in m/s
LF.21: Enter the diameter of the traction sheave in mm, if necessary,
remeasure
LF.22: Enter gear reduction, if necessary, count
LF.23: Enter rope suspension (1 for 1:1, 2 for 2:1 etc.)
LF.24: Enter nominal load (lifting capacity) of the cabine in kg
LF.30: Select control procedure (0 = without feedback, 2 = with
feedback)
LF.40: Enter correction speed in m/s
LF.41: Enter crawl speed in m/s
LF.42: Enter rated speed in m/s
LF.43: Enter inspection speed in m/s
dr.00: Enter rated motor power in kW (1 kW = 1.36 PS)
dr.01: Enter rated motor speed in rpm (not synchronous speed)
dr.02: Enter rated motor current in A
dr.03: Enter rated motor frequency in Hz
dr.04: Enter cos phi of the motor
dr.12: Enter rated motor voltage in V (if the value to be adjusted is
already entered, it is essential to acknowledge the value with
ENTER)
EC.01: Enter encoder pulse number
With inspection speed check, whether the lift moves. In case of error
message „E.EnC“ execute an encoder track change with EC.2=1.
Reset the error message through switch off and switch on.