GB-23
Display
Significance
noP
No Operation; term. X2.1 (control release) is not assigned.
LS
Low speed; control release is set, no direction of rotation
selected, modulation off.
Facc
Forward acceleration; acceleration phase forward.
Fcon
Forward constant running; constant drive forward.
Fdec
Forward deceleration; deceleration phase forward.
racc
Reverse acceleration; acceleration phase reverse.
rcon
Reverse constant running; constant drive reverse.
rdec
Reverse deceleration; deceleration phase reverse.
bbl
Base-block-time; power modules are locked for 3s (always,
if control release is switched off or when an inverter error
occurs) .
a) Running Messages
Inverter State
Operating Parameter
Display
Significance
E.buS
Error, bus, failure in serial communication
E.dOH
Error, drive-overheat, motor overheats and prewarning
time has run out
E.dSP
Error, digital signal processor, error in signal processor
E.PrF
Error, prohibited rotation forward, error in the software
limit switch (when the set direction of rotation is forward,
the software limit switch for forward is inactive)
E.Prr
Error, prohibited rotation reverse, error in the software
limit switch (when the set direction of rotation is reverse,
the software limit switch for reverse is inactive)
E.hyb
Error, hybrid, error in the encoder input card
E.EnC
Error, encoder, error in the encoder break (reset only
possible with Power-On-Reset)
E.LSF
Error, load shunt fault
E.OC
Error, overcurrent, overcurrent short-time peak overloading
E.OH
Error, overheated, overheating of the inverter
E.OH2
Error, overheat 2, electronic motor protection
E.nOH
Error, no overheat, overheating no longer preset, can be
reset (valid for malfunction E.OH or E.OH2)
E.OL
Error, overload, continuous overload, for cooling down
the inverter has to stay supplied with power, the cooling
time depends on the previous overload time
E.OL2
Error overload, overloading of the inverter at output
frequency < 3 Hz
E.nOL
Error, no overload, cooling time has run out, error can be reset
E.OP
Error, overpotential, overvoltage in the DC voltage circuit
E.OS
Error, overspeed, overspeed (can only be reset with
power-on-reset)
E.PuC
Error, power unit code, invalid power circuit recognition
E.SEt
Error, set, set selection error, check LF.02
E.UP
Error, underpotential, undervoltage im DC voltage circuit
b)
Error messages
Summary of Contents for COMBIVERT F4-F