6
1
KEB COMBIVERT F5-M / S
16
Name: Basis
12.05.04
Chapter
Section
Page
Date
©
KEB Antriebstechnik, 2002
All Rights reserved
Functional Desription
Operating and Unit Data
Adr.
min
max
default
022Dh
ru.45
Act. carrier frequency
1
-
-
4
0
Shows the actual carrier frequency of the inverter. The displayed value corresponds to following switching frequencies:
0 = 2 kHz
3 = 12 kHz
1 = 4 kHz
4 = 16 kHz
2 = 8 kHz
Adr.
min
max
default
022Ch
ru.44
Timer 2 display
0,01
-
-
655,35
0
The count of the free-programmable timer 2 is indicated. The display shows optionally seconds, hours or edges/100
(see LE.26). The counter can be adjusted to any chosen value by keyboard or bus. The programming of the counter is
done with the parameters LE.22...LE.26 (also see Chapt. 6.9.4 ÑTimerì).
Adr.
min
max
default
022Eh
ru.46
Motor temperature
1
∞
C
-
255: off
0
Indicates the current motor temperature. Precondition for this function is aspecial power circuit. The temperature detection
is connected to the terminals T1/T2.
0:
T1/T2 closed
253, 254:
broken cable; short circuit; detection error
255:
T1/T2 open
Adr.
min
max
default
022Fh
ru.47
Actual torque limit mot.
0,01
Nm
-
10000
-10000
This parameter displays the currently adjusted set torque limit for motoric operation.
Adr.
min
max
default
0230h
ru.48
Actual torque limit gen.
0,01
Nm
-
10000
This parameter displays the currently adjusted set torque limit for generatoric operation.
-10000