287
Diagnostics and Troubleshooting
*Additional information at end of section
Error/Message Alt. /
(NUM)
Description
Cause/Solution/Troubleshoot
no Error
Overload Low
Speed
nEOL2
(20)
No more
overload.
Error Overload Low speed has cleared and can be reset.
no Error Motor
Overheat
nEdOH
(11)
Over temperature
reset possible
Motor overheat sensor reset and Error Motor Overheat
can be reset.
no Error
Overload
nEOL
(17)
No more
overload.
Overload counter has reached 0%, allowing motor to
cool and the error overload error may be reset.
Power Unit Not
Ready
no_PU
(13)
Control card is
powered up,
but the power
stage is not, so
consequently it
is not seen by
control card.
The Power Unit Not Ready message may occur due to
the following conditions:
Control card powered up by external power supply, but
drive is not powered up by line. Since the drive is not
being powered by the line, the power stage cannot be
identified.
Connection issue between control card and power
stage.
For inverter housing sizes G, H, R, U, remove
then reconnect the ribbon cable connecting the
control card to the power stage at the control card
connection.
For inverter housing sizes D, E, remove the control
card then re-seat, ensuring pin connections.
Switching power supply.
If reseating the ribbon cable does not resolve the
issue, then there may be a failure of the switching
power supply and the drive would need to be
replaced or inspected and repaired by KEB.
Serial
Command
Speed Error
(166)
Serial speed
command not
present at the
beginning of a
run
When US04 = Serial Speed DIN66019 Service 49
(4), Serial Speed DIN66019 Service 50 (5), the speed
command must be received within t=2.5(LT01+LT03) sec.
at beginning of run. Not active on inspection run.Refer to
additional information at end of section