4 | Connection of the control
KEB Automation KG
18
ma_dr_f6-cu-p-inst-20182705_en
Name
DI1…DI8
Terminals
X2A.1…X2A.8
Classification
Low level (logical 0)
-3 … +5 V / 3 mA
High level (logical 1)
11 … 30 V / 2 … 6 mA
Special features
DI1 is switchable via software as analog input
AN3.
Connection
Internal voltage supply
External voltage supply
4
6
8
3
2
1
5
7
16
4
6
8
3
2
1
5
7
9
+
4.2.2 Digital Outputs
Specification
Number
4 (2 at X2A and 2 at X2B)
Name
DO1 … DO4
Terminals
X2A.10, X2A.12
Type
24 V high-side switch
Classification
Output voltage
Minimum P24Vin – 3 V
maximum P24Vin
Output current
Maximum 100 mA per output (short-circuit proof)
Special features
only ohmic load; no internal free-wheeling path