Connection of the control | 4
ma_dr_f6-cu-p-inst-20182705_en
21
Input signals
Current/voltage switchable
Voltage input
DC 0…±10 V
Current input
DC 0…±20 mA; DC 4…20 mA
Common mode range
-12.5 V…17.5 V
Connection
Connection of the analog differential inputs AN1 and AN2
20
22
19
18
17
21
+
*
0…±10Vdc
+
0…±20mA
4…20mA
*) Equipotential bonding conductor
4.2.4.2 Absolute input
Specification (absolute input)
Number
1
Name
AN3
Terminals
X2A.1 switchable via software as digital/
analog input)
Classification
non-isolated absolute input
Input signals
Voltage
Voltage input
DC 0.2…10 V / max. 5 mA
Others
Is not intended for control with poten-
tiometer. The voltage source must be
able to supply the input current.
Connection
Connection of the analog absolute input AN3
1
9
+
DC 0,2…10 V
4.2.5 Analog output
Specification
Number
1
Name
ANOUT