4 | Connection of the control
KEB Automation KG
24
ma_dr_f6-cu-p-inst-20182705_en
Observe the input voltage of the device!
a) The connected consumers must be designed for the voltage tolerance of the
voltage output 24VoutCtrl.
Connection for internal supply
27
26
X2A
28
Sehen Sie dazu auch
2
Determination of the current consumption [
4.2.6.1.4 Mixed supply
Mixed voltage supply is used,
• if the controller is to remain in operation when the mains supply of the COMBI-
VERT is switched off.
• so that the COMBIVERT can continue to operate if the external power supply
fails.
Install protective diode
a) The diode D1 prevents the voltage output from supplying other consumers if
the external supply fails.
ACHTUNG
Too much current load!
Malfunctions at the device and in the application.
a) Determine the maximum current according "Determination of the current con-
sumption".
b) If current consumption at P24Vin is higher than max. output current at
24VoutCtrl, then select external or mixed supply.
Observe the input voltage of the device!
a) The connected consumers must be designed for the voltage tolerance of the
voltage output 24VoutCtrl.