GB - 19
Connection of the Power Unit
U, V, W Motor connection
0.2-16 mm²
AWG 26-6
2,3 Nm
20.5 lb-inch
PE,
Connection for
shielding/
earthing
Screw M4 for
ring thimble
1,3 Nm
11 lb inch
3.2.2.7 Wiring of the motor
L1
L2
L3
U
V
W
PE
U
V
W
PE
PE
T1 T2
1 KEB COMBIVERT
2 Apply motor cable, shielding on both sides
over a large surface on the function earth
3 Three-phase motor
4 Temperature monitoring (optional)
see chapter „Temperature detection"
Do not lay PTC cable of the motor (also shielded) together with control cable !
PTC cable inside the motor cable only permissible with double shielding !
3.2.3 Connection of a braking resistor
3.2.3.1 Terminal strip X1B
X1B
Name Function
Cross-section
Tightening
torque
++, PB Connection for bra-
king resistor
0.2-16 mm²
AWG 26-6
2,3 Nm
20.5 lb-inch
PE,
Connection for
shielding/
earthing
Screw M4 for
ring thimble
1,3 Nm
11 lb inch
3.2.3.2 Wiring of an intrinsically safe braking resistor
X1B
++
--
PB
U
V
W
Only „intrinsically safe“ braking resistors are per-
missible for the operation without temperature
monitoring.
See chapter 3.2.5 for an example with extensive
protection.