Start-up
© KEB, 2008-02
COMBIVERT R6-S
Page 4.2 - 5
4
10
Deactivate regeneration
cS.05 Puls off delay, cS.06 puls off level (CP.32)
If the actual power (ru
.81 / CP.13) exceeds the defined value in cS
.06 (CP.32), the modulation is switched off
after expiration of the adjusted time in cS.05.
The
setting for the respective application can be determined as follows:
- Start-up the drive based on the default values and the adjustment via Pn.19 (CS.33).
- Regenerative operation of the drive, e.g. deceleration process.
- Stop the drive (LS), control release at R6 is active. R6 remains in status ‚rEGEn‘.
- Read actual power ru.81 (CP.13) and enter the value plus one offset of approx.10% in cS.06 (CP.32). R6
changes into status ‚Stb‘
- Check adjustment. R6 must always change into status ,Stb‘ after completion of regenerative operation.
- Increase cS.06 (CP.32) if necessary.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......