Operating and appliance data
Parameter
Addr.
R PG E Min. value
Max. value Res. [?] Default
ru.23
Output condition state
0217h ro
-
-
0
255
1
-
-
With parameters do 00...do.07 switching conditions can be selected, that serve as base for setting the out-
puts. This parameter indicates which of the selected switching conditions are met before they are linked or
inverted by programmable logic (also see chapt. 3.3. „Digital outputs“). According to following table a speci-
fic decimal value is given out for the switching conditions. If several of the selected switching conditions are
met, the sum of the decimal values is indicated.
Bit
Decimal value Output
0
1
switching condition 0 (do.00)
1
2
Switching condition 1 (do.01)
2
4
Switching condition 2 (do.02)
3
8
Switching condition 3 (do.03)
4
16
Switching condition 4 (do.04)
5
32
Switching condition 5 (do.05)
6
64
Switching condition 6 (do.06)
7
128
Switching condition 7 (do.07)
Parameter
Addr.
R PG E Min. value
Max. value Res. [?] Default
ru.24
State of
output flags
0218h ro
-
-
0
255
1
-
-
Display of the
output flags after logic step 1. The selected switching conditions are linked in logic step 1
(do.8...24) and indicated here (see chapt. 3.3 „Digital outputs“). According to following table a specific deci
-
mal value is given out for any
output flags. If several output flags are set, the sum of the decimal values is
indicated.
Bit
Decimal value Output
0
1
Flag 0
1
2
Flag 1
2
4
Flag 2
3
8
Flag 3
4
16
Flag 4
5
32
Flag 5
6
64
Flag 6
7
128
Flag 7
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......