Operating and appliance data
© KEB, 2008-02
COMBIVERT R6-S
Page 3.2 - 11
3
10
Parameter
Addr.
R PG E Min. value
Max. value
Res.
[?]
Default
ru.80 Digital output state
0250h
ro
-
-
0
255
1
-
-
With do.51 the digital output signals can be assigned to the hardware outputs (see chapter 7.3.). This para-
meter displays the digital output state of the output signals in accordance with the following table. If several
outputs are set, the sum of the decimal values is displayed.
Bit
Decimal value Output
Terminal
0
1
O1 (transistor output 1)
X2A.19
1
2
O2 (transistor output 2)
X2A.20
2
4
R1 (relay RLA,RLB,RLC)
X2A.24...26
3
8
R2 (relay FLA,FLB,FLC)
X2A.27...29
4
16
OA (internal output A)
no
5
32
OB (internal output B)
no
6
64
OC (internal output C)
no
7
128
OD (internal output D)
no
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.81
Actual power
0251h ro
-
-
-3200,0
3200,0
0,1
kW
0,0
ru.81 displays the actual power of the COMBIVERT R6-S. Motor power is displayed with positive values,
generatoric power is displayed with negative values.
Parameter
Addr.
R PG E Min. value
Max. value
Res.
[?]
Default
ru.82
Total regen
0252h rw
-
-
0
2147483647
1
kWh
0
Counter for the regeneratoric electric work to the mains.
Parameter
Addr.
R PG E Min. value
Max. value
Res.
[?]
Default
ru.83 Total motor
0253h rw
-
-
0
2147483647
1
kWh
0
Counter for the supplied electrical work from the mains.
Parameter
Addr.
R PG E Min. value
Max. value
Res.
[?]
Default
ru.84 Total net
0254h rw
-
-
0
2147483647
1
kWh
0
Display of the difference between supplied and regeneratoric work. The result is displayed right sign and is
depending on the faulty wiring.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
ru.85
Actual net
0255h ro
-
-
0,00
655,35
0,01 kVA
0
Display of the actual net.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......