Page 3.2 - 14
COMBIVERT R6-S
© KEB, 2008-02
Operating and appliance data
Parameter
Addr.
R
PG E Min. value
Max. value Res.
[?]
Default
In.25
Error diagnosis
0E19h
ro
+
-
0
65535
1
-
0
Shows the last errors that occurred (in the sets 0...7). The oldest error is in set 7. A new error is stored in
set 0. All other errors are shifted to the next parameter. The oldest error is not applicable. The display of the
error occurs in the highest word (Bit 12…15).
A difference time is determined between errors of the same type (e.g. double OC). This time is stored in the
three low-order words. The display occurs in hexadecimal code.
Error
Difference time
Value
Bit
Bit
Bit
Bit
15…12
11…8 7…4 3…0
X
0
0
0
0 min.
X
0
0
1
1 min.
X
:
:
:
:
X
F
F
E
4094 min.
X
F
F
F
> 4095 min.
0
X
X
X
no error
1
X
X
X
E.OC
2
X
X
X
E.OL
3
X
X
X
E.OP
4
X
X
X
E.OH
5
X
X
X
E.OHI
Example:
The following values are
displayed:
Set 0:
3000
Set 1:
2000
Set 2:
4023
Set 3:
4000
Set 4-7:
0000
Explanati-
on:
The error that occurs last is stored in set 0. In the table the highest hex-value „3“ indicates
error E.OP (overvoltage).
Before it error E.OL (set 1=2xxx) occurs. Since the errors are of different types, no difference
time was stored.
Error E.OH is stored in set 2 and 3. Since the errors are of the same type, a diffenrence time
(here „023 “) is stored in the three low-order words of set 2. The value of 23 hexadecimal
corresponds decimal to a difference time of 35 minutes.
No errors are stored in set 4…7.
Parameter
Addr.
R PG E Min. value Max. value Res.
[?]
Default
In.26 E.OC error counter
0E1Ah
rw
-
-
0
65535
1
-
0
In.27 E.OL error counter
0E1Bh
In.28 E.OP error counter
0E1Ch
In.29 E.OH error counter
0E1Dh
In.30 E.OHI error counter
0E1Eh
The error counters (for E.OC, E.OL, E.OP, E.OH, E.OHI) specify the total number of errors of each error
type.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......