Operating and appliance data
© KEB, 2008-02
COMBIVERT R6-S
Page 3.2 - 15
3
10
3.2.6 Description of the Sy-Parameters
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.02
Inverter identifier
0002h rw
-
-
4000
4002
1
-
-
An unique number is assigned to each inverter type which identifies the COMBIVERT. This value is used
for example by COMBIVIS to
load the correct configuration files.
SY.02 can be written with the indicated
value (e.g. for identification of download lists).
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.03 Power unit code
0003h rw
-
+
0
32767
1
-
-
On the basis of the power circuit identification the control recognizes the used power circuit, respectively a
change of the power circuit and adjusts certain parameters accordingly. To accept a new P-Id enter positive
values (see chap. 5 „E.Puch“).
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.06 Inverter address
0006h rw
-
+
0
239
1
-
1
In SY.06 can be adjusted, if the COMBIVERT shall be responded via „COMBIVIS“ or another control.
Values between 0 and 239 are possible, the default value is 1. If several COMBIVERT are operated on
the bus simultaneously, it is absolutely necessary to assign different addresses to them, since otherwise it
leads to communication failures because several COMBIVERT may answer at the same time. The descrip-
tion of the DIN 66019II protocol (C0.F5.01I-K001) contains further information to this.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.07
Baud rate ext. bus / PC
0007h rw
-
+
0
6
1
-
3
Following values for the baud rate of the serial interface are possible
:
Parameter value
Baud rate
0
1,2 KBaud
1
2,4 KBaud
2
4,8 KBaud
3 (default)
9,6 kBaud
4
19,2 kBaud
5
38,4 kBaud
6
55,5 kBaud
If the value for the baud rate is changed via the serial interface, it can be changed again only by the key-
board or after adapting the baud rate of the master, as no communication is possible with different baud
rates of master and slave.
Should problems occur at the data transmission choose a transmission rate of maximal 38,4 Baud.
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.09 HSP5 watchdog time
0009h rw
-
+
0 (off)
10,00
0,01
s
0 (off)
The HSP5 watchdog function monitors the communication of the HSP5 interface (control card - operator;
or control card - PC). After expiration of an adjustable time (0,01...10 s) without incoming telegrams, the
response adjusted in Pn.5 is triggered. The value „off“ deactivates the function.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......