Operating and appliance data
© KEB, 2008-02
COMBIVERT R6-S
Page 3.2 - 19
3
10
Parameter
Addr.
R PG E Min. value
Max. value Res.
[?]
Default
SY.51 Status word low
0033h ro
-
-
0
65535
1
-
0
The current condition of the COMBIVERT can be readout with the status word. The status word long
(SY.44) consists of the two 16 bit parameters status word high (SY.42) and status word low (SY.51). The
status word is bit-coded.
Bit
Value
Description
0
1:
ST
1=set control release (AND operation with di.1 bit 0)
1
2: Error
Inverter is in error state
2
0: Stop
The modulation is switched off at „stop“ and switched on at
„start“.
Exception: If a positioning is stopped with bit 11 "stop" in the
control word, "stop" is displayed in the status word, if the drive re-
aches speed 0 (even if modulation is still active). This exception
can be reversed with bit 9 in parameter Pn.65 „special functions“.
4: Start
3
0: Clockwise
rotation
Display of the actual direction of rotation
8: Counter-clockwise rotation
4...6
0: Set 0
Display of the actual parameter set.
16: Set 1
32: Set 2
48: Set 3
64: Set 4
80: Set 5
96: Set 6
112: Set 7
7
128: Actual value = Setpoint
value
ru.07 „actual value display" with a hysteresis of +/- LE.16 „freq./
speed hysteresis“ has the same value as ru.01 „set value dis-
play“
8
256: Fast stop
Fast stop is active
9
512: HSP5 bus-synchronous
Inverter in bus-synchronous operation
10
1024: Approach to reference
point completed
Approach to reference point was executed since the last power
on (or the position was validate otherwise)
11
2048: Position reached
Display that the
position profile is completed and the drive is in
the range of +/- PS.30 „target window“ near ru.61 „target positi-
on“
12, 13
0: Speed control
Display of the operating mode selected via control word
(only identical with the actual operating mode of the inverter, if in
PS.00 „pos/syn
mode“ in bits 0..2 value „7: via control word“ is
programmed)
4096: Synchronous running
8192: Positioning
12288: Contouring control
14
Posi or approach to reference
point active
Positioning or approach to reference point is active
15
internal limit
The speed setpoint value or any controller (e.g.
current, flux,
speed or external PID controller) is in limitation (also in V/f cha-
racteristic open-loop operation)
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......