Page 3.3 - 6
COMBIVERT R6-S
© KEB, 2008-02
Analog outputs
Analog output as switch
An example for the use of the analog output as 0/10V switch is shown in picture 7.2.5.c
1. set the gain (An.33) to 20.00
2. set X-offset (An.34) to the desired switching level
Picture 7.2.5.c Analog output as switch
10V
100%
-100%
-100%
An.34
100%
An.33
Due to the high gain the analog output switches in a relative small switching window.
Calculation of the gain
Since the analog output works always to the
specified values in 7.2.4 the characteristic can be adjusted with
the gain so that the total range of 0… ±10V is used.
specified value
–––––––––––––––
desired value
= gain (An.33 / 43 / 49)
3.3.6 ANOUT 1 value (An.32 / 42 / 48)
Analog values for the respective input can be preset in percentage with parameters An.32/An.42/An.48.Value
8
:
„Digital setting“ must be adjusted as process variable. The setting is in the range of ±100 %.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......