COMBIVERT R6-S
© KEB, 2008-02
Product overview
1.2.3 Functional principle
After switching on the DC interconnection is supplied with voltage after correct initialisation phase. If the voltage
in the DC interconnection exceeds an adjustable threshold due to generative operation, the COMBIVERT R6-S
starts to regenerate the energy into the net by square-wave modulation. The COMBIVERT can synchronize to
mains frequency
by a sychronization module in front of the commutation throttle, or harmonic filter, so regenera
-
tion is done synchronously to the mains frequency.A sine-wave current is formed of it
at the harmonic filter. The
compliance with the requirements in accordance with EN 61000-3-12 is secured only by the harmonic filter
.
If the regenerative power decreases an adjustable value, the COMBIVERT R6-S switches off the regeneration
after expiration of a turn-off delay and it will be turn into motoric operation.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......