Page 4.1 - 4
COMBIVERT R6-S
© KEB, 2008-02
Start-up
Before switching on the inverter go through the following checklist.
Is the COMBIVERT firmly bolted in the control cabinet?
Is there enough space to ensure sufficient air circulation?
Are mains and DC cables as well as the control cables installed separately from each other?
Are all mass and earthing cables attached and well contacted?
Check, whether all power and control cables are firmly in place!
Remove any tools from the control cabinet!
Attach all covers and protective caps to ensure that all live parts are secured against direct contact.
When using measuring instruments or computers an isolating transformer should be used, if not, make
sure that the equipotential bonding between the supply lines is guaranteed!
Open the control release of the COMBIVERT to avoid the unintended starting of the machine.
Instructions to the wiring can be taken from the installation manual!
4.1.4 Safety instructions
General instructions
Electric
Shock
COMBIVERT R6 power supply and regenerative units contain dangerous voltages which
can cause death or serious injury.
COMBIVERT R6 can be adjusted by way that energy is refeed into the supply system in
case of power failure at regenerative operation. Therefore a dangerous high tension can
exist in the unit after switching off the supply system.
Before working with the unit check the isolation from supply by measurements in the
unit.
Care should be taken to ensure correct and safe operation to minimise risk to personnel
and equipment.
Only Qualified
Electro-Perso-
nnel
All work from the transport, to installation and start-up as well as maintenance may only be
done by qualified personnel (IEC 364 and/or CENELEC HD 384 and IEC-Report 664 and
note national safety regulations). According to this manual qualified staff means those who
are able to recognise and judge the possible dangers based on their technical training and
experience and those with knowledge of the relevant standards and who are familiar with
the field of power transmission.
Observe Stan-
dards
The COMBIVERT R6 must not be started until it is determined that the installation com-
plies with 2006/42/EC (machine directive) as well as the EMC directive (2004/108/EC)(note
EN60204).
The COMBIVERT R6 meets the requirements of the Low-Voltage Directive 2006/95/EC.
The harmonized standard of the series EN 61800-5-1 (VDE 0160) is used.
This is a product of limited availability in accordance with IEC 61800-3. This product may
cause radio interference in residential areas. In this case the operator may need to take
corresponding measures.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......