3.4 Digital in- and outputs
3.4.1 Short description digital inputs
The KEB COMBIVERT R6 has 5 external digital inputs and 5 internal inputs (ST, I1…I3). All inputs can be as-
signed to one or several functions.
Beside the terminal strip parameter di.00 determines whether the external inputs are controlled in PNP or NPN
circuit. Parameter ru.21 displays the actual controlled inputs. Each input can be set either (di.01) via terminal
strip or via software with
di.02. A digital filter (
di.03) decreases the noise sensitivity of the inputs. The inputs
can be inverted with di.04 and switched to slope-triggering with di.05. A strobe mode can be activated with
parameters di.06...di.08. The internal input state (ru.22) displays the actual inputs set for further processing.
The function/-s, which are executed by a programmable input is determined with the input selection of the ap-
propriate function or di.11...22.
The control release (ST) must be switched generally by hardware for safety reasons. Edge-triggering, inversion
and strobe
signal can be adjusted, but they have no influence.
Picture 7.3.1 Principle of the digital inputs
Terminal
strip
2A.12...16
4
di.0
di.2
di.1
di.3
di.4
1
di.5
12
12
di.8
di.7
di.6
12
1
ru.2 1
ru.2 2
12
7
12
8
Sy.43
≥
1
Assign-
ment of
the inputs
X2A.16
internal
inputs
ST,
I1...I3
The input I4 is directly connected by hardware with the master- / slave control. Master is input, slave is output.
The input is also available for additional functions.
PNP/
NPN
Terminal
state
Input
state
Strobe
mode
select digi-
tal input
Digital
filter
select
strobe
input
Control
word long
X2A.16 is dependent of
Pn.19: master (=
output) or slave (= input)
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......