Digital in- and outputs
© KEB, 2008-02
COMBIVERT R6-S
Seite 3.4 - 5
3
10
Picture 7.3.3 Control digital inputs by software (di.01/di.02)
Terminal strip
&
&
SY.50 Bit 0 = 1
di.01
di.02
1 128 256 512 1024 2048
ST
I4
IA
IB
IC
ID
ST
I4
IA
IB
IC
ID
1
128
256
512
1024
2048
Internal inputs
As shown in picture 7.3.3 it can be selected with di.01 whether the inputs are switched by terminal strip (def-
ault) or via parameter di.02 . The two parameters are bit-coded, i.e. in accordance with the following table the
associated value of the input must be entered. With several inputs the sum is to be formed.
(Exception: control release must always be bridged at the terminal strip).
Table terminal status
Bit Decimal value Input
Terminal
0
1
ST (prog. input „control release/ reset“)
X2A.12
1
2
RST (prog. input „reset“)
no
2
4
F (prog. input)
no
3
8
R (prog. input)
no
4
16
I1 (prog. input 1)
X2A.13
5
32
I2 (prog. input 2)
X2A.14
6
64
I3 (prog. input 3)
X2A.15
7
128
I4 (prog. input 4)
X2A.16
8
256
IA (internal input A)
no
9
512
IB (internal input B)
no
10
1024
IC (internal input C)
no
11
2048
ID (internal input D)
no
Example: ST, F and IB are controlled
, displayed value = 1+4+512 = 517
3.4.4 Input terminal state (ru.21), internal input state (ru.22)
The input terminal state (ru.21) displays the logical levels at the input terminals. It is irrelevant whether the
inputs are internally active or not. If a terminal is controlled, the appropriate decimal value according to table
„Terminal status“ is output. With several active terminals the sum of the decimal values is output.
The internal input state (ru.22) displays the logical state of the digital inputs set internally for processing. If an
input is set, the appropriate decimal value according to the table 7.3.1 is output. If several inputs are set, the
sum of the decimal values is output.
Summary of Contents for combivert R6-S
Page 1: ...APPLICATION MANUAL Mat No Rev 00R6SEA K130 1 A GB KEB COMBIVERT R6 S Version 1 3 ...
Page 2: ...Page 1 1 2 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 4: ...Page 1 1 4 COMBIVERT R6 S KEB 2008 02 Introduction ...
Page 14: ...Page 1 2 6 COMBIVERT R6 S KEB 2008 02 Product overview ...
Page 28: ...Page 2 1 6 COMBIVERT R6 S KEB 2008 02 Fundamentals ...
Page 34: ...Page 2 2 6 COMBIVERT R6 S KEB 2008 02 Password structure ...
Page 116: ...Page 3 8 2 COMBIVERT R6 S KEB 2008 02 Special functions 3 8 1 Program timer counter 3 8 3 ...
Page 130: ...Page 3 9 10 COMBIVERT R6 S KEB 2008 02 Define CP Parameters ...
Page 140: ...Page4 2 2 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 144: ...Page4 2 6 COMBIVERT R6 S KEB 2008 02 Start up ...
Page 150: ...Page 5 1 6 COMBIVERT R6 S KEB 2008 02 Error assistance ...
Page 158: ...Page 6 1 8 COMBIVERT R6 S KEB 2008 02 Project design ...
Page 160: ...Seite 7 1 2 COMBIVERT R6 S KEB 2008 02 Annex 7 1 1 Keyword index 7 1 3 ...
Page 166: ......
Page 167: ......